Ademco - Vista 100 Installation Manual

File Preview
File Preview
Click below to download for free

File Data

Name ademco-vista-100-installation-manual-9175308426.pdf
Type PDF
Size 2.02 MB
Downloads

Text Preview

VISTA 100 FIRE AND BURGLARY SECURITY SYSTEM SCHEDULING INSTRUCTIONS GUIDE N6019 2 1 96 FOR PROPER PROTECTION Following Recommendations For The Location Of Fire And Burglary Detection Help Provide Proper Coverage For The Protected Premises For Smoke And Heat Detectors regard to the number and placement of smoke heat detectors we subscribe to the contained in the National Fire Protection Association NFPA Standard 72 below warning fire detection is best achieved by the installation of fire detection equipment all rooms and areas of the household as follows For minimum protection a smoke detector be installed outside of each separate sleeping area and on each additional floor of a family living unit including basements The installation of smoke detectors in attics finished or unfinished or in garages is not normally recommended additional protection the NFPA recommends that you install heat or smoke detectors in living room dining room bedroom s kitchen hallway s attic furnace room utility and rooms basements and attached garages addition we recommend the following a smoke detector inside every bedroom where a smoker sleeps a smoke detector inside every bedroom where someone sleeps with the door partly or closed Smoke could be blocked by the closed door Also an alarm in the hallway may not wake up the sleeper if the door is closed a smoke detector inside bedrooms where electrical appliances such as portable air conditioners or humidifiers are used a smoke detector at both ends of a hallway if the hallway is more than 40 feet 12 long smoke detectors in any room where an alarm control is located or in any room where control connections to an AC source or phone lines are made If detectors are not so a fire within the room could prevent the control from reporting a fire or an intrusion ROOM ROOM ROOM Detectors for Minimum Protection Detectors for Additional Protection Detectors RM CLOSED This control complies NFPA requirements for pulse sounding of notification devices For Proper Intrusion Protection proper intrusion coverage sensors should be located at every possible point of entry to a home or premises This would include any skylights that may be present and the upper windows in a building addition we recommend that radio backup be used in a security system so that alarm signals can still sent to the alarm monitoring station in the event that the telephone lines are out of order alarm signals normally sent over the phone lines if connected to an alarm monitoring station ii OF CONTENTS TO USE THIS MANUAL USED IN THIS MANUAL FOR PROPER PROTECTION 4 1 2 DESCRIPTION A PARTITIONED SYSTEM of Partitioning Up a Partitioned System Lobby Logic 3 MOUNTING THE CONTROL PC BOARD LOCK the Cabinet The Cabinet Lock A Mercantile Premises Listing A Mercantile Safe and Vault Listing the Control Circuit Board the AC Transformer the Backup Battery Earth Ground Connections MECHANICS OF PROGRAMMING Data Field Program Mode and Communication Defaults Data Field Programming Mode from One Page of Programming to Another Data Fields Errors System Wide Data Fields Partition Specific Data Fields Menu Mode Programming THE KEYPADS That May Be Used To The Keypads a Supplementary Power Supply the Keypads the Keypads Preliminary Check out Procedure Remote Keypads HARDWIRED ZONES 001 008 Characteristics of Hardwired Zones 1 8 Burglary and Panic Devices to Zones 1 8 2 Wire Smoke Detectors to Zones 1 and 2 2 Wire Smoke Detectors 4 Wire Smoke Detectors to Zones 1 8 4 Wire Smoke Detectors 2 Wire Latching Glass Break Detectors To Zone 8 Glass Break Detectors Hardwired Zones Procedure For Hard Wired Zones 6 5 iii 7 LOOP EXPANSION Characteristics of Polling Loop Zones RPM Devices Loop Supervision Polling Loop Zones Procedure For Polling Loop Zones Polling Loop Devices 8 WIRELESS ZONE EXPANSION Characteristics of Wireless Zones Systems Available

Related Files