Ademco - Vista 10SE Installation Manual
File Preview
Click below to download for free
Click below to download for free
File Data
Name | ademco-vista-10se-installation-manual-9271456380.pdf |
---|---|
Type | |
Size | 1.52 MB |
Downloads |
Text Preview
Security System ISSUE INCLUDES THE NEW QUICK ENROLLMENT DEVICES PROCEDURE FOR 5800 SERIES TRANSMITTERS Instructions Installation Instructions Installation Instructions 5 97 FOR PROPER PROTECTION following recommendations for the location of fire and burglary detection help provide proper coverage for the protected premises For Smoke And Heat Detectors regard to the number and placement of smoke heat detectors we subscribe to the contained in the National Fire Protection Association NFPA Standard 72 noted warning fire detection is best achieved by the installation of fire detection equipment in all and areas of the household as follows For minimum protection a smoke detector should installed outside of each separate sleeping area and on each additional floor of a multi floor living unit including basements The installation of smoke detectors in kitchens attics or unfinished or in garages is not normally recommended maximum protection the NFPA recommends that you install heat or smoke detectors in the room dining room bedroom s kitchen hallway s attic furnace room utility and storage basements and attached garages addition we recommend the following a smoke detector inside every bedroom where a smoker sleeps a smoke detector inside every bedroom where someone sleeps with the door partly or closed Smoke could be blocked by the closed door Also an alarm in the hallway may not wake up the sleeper if the door is closed a smoke detector inside bedrooms where electrical appliances such as portable air conditioners or humidifiers are used a smoke detector at both ends of a hallway if the hallway is more than 40 feet 12 long smoke detectors in any room where an alarm control is located or in any room where control connections to an AC source or phone lines are made If detectors are not so a fire within the room could prevent the control from reporting a fire or an intrusion ROOM ROOM ROOM Detectors for Minimum Protection Detectors for Additional Protection Detectors RM CLOSED CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL SOUNDING FOR FIRE NOTIFICATION APPLIANCES For Proper Intrusion Protection proper intrusion coverage sensors should be located at every possible point of entry to a home or premises This would include any skylights that may be present and the upper windows in multi level building addition we recommend that radio backup be used in a security system so that alarm signals can be sent to the alarm monitoring station in the event that the telephone lines are out of order alarm are normally sent over the phone lines if connected to an alarm monitoring station 2 OF CONTENTS 1 DESCRIPTION 2 3 4 THE CONTROL the Cabinet the Lock if used the Control Circuit Board Alone or if used With a 4204 Relay Unit Control and RF Receiver Circuit Boards Together in the Cabinet Phone Line Connections the AC Transformer the Back Up Battery Ground Connections REMOTE KEYPADS that May Be Used to the Keypads Run Chart for Devices Drawing AUX Power From the Control the Keypads A Supplementary Power Supply To Power Additional Keypads Check Out Procedure HARD WIRED ZONES 1 the Hard Wired Zones Characteristics For Zones 1 Burglary and Panic Devices to Zones 1 4 Wire Smoke Combustion Detectors on Zones 5 4 Wire Smoke Combustion Detectors Hard Wired Zones Panic Keys Procedure for Hard Wired Zones 1 5 WIRELESS RF ZONE EXPANSION 5700 5800 RF SYSTEMS Systems Available System Operation and Transmitter Supervision Battery Life Supervision and Setup of the 4281 5881 Series Wireless Receivers the 5800TM Module Series Transmitter Setup the DIP Switches on 5700 Series Wireless Transmitters Zone ID Assignments for 5700 Series Transmitters Switch Tables for 5700 RF System Wireless Devices 5700 Series Transmitters the Control For a 5700 Wireless System the House ID Sniffer Mode 5700 Systems Programming for 5700 Series Transmitters Test Series Transmitter Setup Series Transmitter Input Loops Series Transmitter Input Types 5800 Series Transmitters the RF Transmitters 5800 RF Systems 5800 Transmitters Into the System Through Zone Programming Q 56 3 5 WIRELESS RF ZONE EXPANSION 5700 5800 RF SYSTEMS CONT Either Temporarily or Permanently Remove a Zone From the System 5800 System