Ademco - Vista 15 Installation Manual
File Preview
Click below to download for free
Click below to download for free
File Data
Name | ademco-vista-15-installation-manual-4789301562.pdf |
---|---|
Type | |
Size | 2.30 MB |
Downloads |
Text Preview
9,67 cid 16 cid 20 cid 24 4 00 Installation Setup Guide FOR PROPER PROTECTION Following Recommendations for the location of Fire and Burglary Detection Help Provide Proper Coverage for the Protected Premises for Smoke and Heat Detectors regard to the number and placement of smoke heat detectors we subscribe to the recommendations in the National Fire Protection Association NFPA Standard 72 noted below warning fire detection is best achieved by the installation of fire detection equipment in all rooms areas of the household as follows For minimum protection a smoke detector should be installed of each separate sleeping area and on each additional floor of a multi floor family living unit basements The installation of smoke detectors in kitchens attics finished or unfinished or garages is not normally recommended additional protection the NFPA recommends that you install heat or smoke detectors in the living dining room bedroom s kitchen hallway s attic furnace room utility and storage rooms and attached garages addition we recommend the following Install a smoke detector inside every bedroom where a smoker sleeps Install a smoke detector inside every bedroom where someone sleeps with the door partly or closed Smoke could be blocked by the closed door Also an alarm in the hallway outside not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical appliances such as portable heaters air or humidifiers are used Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet 12 meters long Install smoke detectors in any room where an alarm control is located or in any room where alarm connections to an AC source or phone lines are made If detectors are not so located a fire the room could prevent the control from reporting a fire or an intrusion CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES ROOM ROOM ROOM Detectors for Minimum Protection Detectors for Additional Protection Detectors RM CLOSED for Proper Intrusion Protection proper intrusion coverage sensors should be located at every possible point of entry to a home or premises This includes skylights and upper windows in a multi level building addition we recommend that radio backup be used in a security system so that alarm signals can still be to the alarm monitoring station in the event that the telephone lines are out of order alarm signals are sent over the phone lines if connected to an alarm monitoring station of Contents Used In This Manual viii 1 Introduction 1 1 2 Installing the Control 2 the Cabinet 2 the Lock if used 2 the Control Circuit Board Alone in the Cabinet 2 Control and RF Receiver Circuit Boards Together in the Cabinet 2 Phone Line Connections 2 the AC Transformer 2 the Backup Battery 2 Ground Connections 2 3 Installing Remote Keypads 3 That May Be Used 3 to the Keypads 3 the Keypads 3 Power for Additional Keypads 3 Checkout Procedure 3 4 Basic Hardwired Zones 1 4 the Hardwired Zones 4 Hardwired Zones 4 Procedure for Hardwired Zones 4 5 Wired Zone Expansion 5 Zone Expansion Units 5 and Setup 5 Wired Expansion Zones 5 Procedure for Wired Expansion Zones 5 6 Wireless Expansion 5800 System 6 Wireless Expansion 6 the 5881 5882 Receiver 6 the 5800TM Module 6 Detection and Reporting 6 5800 Series Transmitters