Autocall E-Series Analog Heat Sensor A4098-9733E and Bases for Extended Exposure to High Humidity
File Preview
Click below to download for free
Click below to download for free
File Data
Name | autocall-e-series-analog-heat-sensor-a4098-9733e-and-bases-for-extended-exposure-to-high-humidity-9672453018.pdf |
---|---|
Type | |
Size | 959.47 KB |
Downloads |
Text Preview
Datasheet Initiating Peripherals Analog Heat Sensor A4098 9733E and Bases for Extended Exposure to High ULC CSFM Listed FM heat sensors provide analog thermal information to the base and feature Epoxy encapsulated electronic thermal sensor design with gold plated high humidity thermistor and stainless steel screws A fast response thermistor that is inherently rate compensated Operation for ceiling or wall mounting sensor bases features Digital transmission of analog sensor values via IDNet Base mounted address remains with its location Integral red LED for power on pulsing or alarm or trouble steady on Locking anti tamper design mounts on standard box Designed for EMI compatibility Magnetically operated functional test options and accessories include Control of supervised or unsupervised remote relay Remote LED alarm indicator output Relays and LED alarm indicators Communications isolator base or sounder base alarm control panel provides Fixed temperature sensing rate of rise temperature sensing or both Utility temperature sensing Automatic once per minute individual sensor calibration check that sensor integrity Ability to display and print detailed sensor information in plain English use with the following Autocall products 4007ES 4010ES and 4100ES Series control panels listed to Standard 521 for 60 ft x 60 ft 18.3 m spacing for 135 F 57.2 C alarm 40 ft x 40 ft 12.2 m spacing for 155 F 68 C alarm Sounder operation is also listed to UL Standard 464 as an audible appliance most fires hazardous levels of smoke and toxic gas can build before a heat detection device would initiate an alarm In cases Life Safety is a factor the use of smoke detection is highly heat sensors heat sensors are self restoring and provide rate fixed temperature sensing selectable with or without temperature sensing Due to its small thermal mass sensor thermistor accurately and quickly measures the local for analysis at the fire alarm control panel 1 Heat Sensor in Standard Size Base 2 Heat Sensor Mounted in Sounder Base Selection temperature detection is selectable at the control panel for 15 F 8.3 C or 20 F 11.1 C per minute Fixed temperature is independent of rate of rise sensing and programmable to at 135 F 57.2 C or 155 F 68 C In a slow developing fire temperature may not increase rapidly enough to operate the rate feature However an alarm will be initiated when the temperature its rated fixed temperature setting Device Temperature Monitoring device temperature monitoring can be programmed to monitor temperature extremes in the range from 32 F to 155 F 0 C to 68 This feature can provide freeze warnings or alert to HVAC system Refer to specific panels for availability Communication of Analog Sensing bases contain integral addressable electronics that monitor information from the detachable heat sensors Each sensor is digitized and transmitted to the system fire alarm control approximately every four seconds using Autocall addressable The panel processes the information to evaluate for alarm levels or other off normal conditions Alarm and Trouble LED Indication sensor base LED pulses to indicate communications with the If the control panel determines that a sensor is in alarm or has other type of trouble the details are annunciated at the control and that sensor base LED will be turned on steadily During a alarm the control panel will control the LEDs such that an LED a trouble will return to pulsing to help identify the alarmed This product has been approved by the California State Fire Marshal CSFM pursuant to Section 13144.1 of the California Health and Safety Code See CSFM Listings 7300 2269 0550 7300 269 0531 7300 2269 0538 7300 2269 0503 7270 2269 0512 and 7300 2269 0551 for allowable values and or conditions concerning material presented in this document Additional listings be applicable contact your local Autocall product supplier for the latest status Rev 9 03 2021 Analog Heat Sensor A4098 9733E and Bases for Extended Exposure to High Humidity Reference sensor locations should be determined only after careful consideration of the physical layout and contents of the area to be protected Refer NFPA 72 the National Fire Alarm and Signaling Code For detailed application information refer to A4098 Detectors Sensors and Bases Application 574 709AC LED Alarm Indicator bases located out of easy viewing the A2098 9808 remote red LED alarm indicator duplicates the base LED status indication It is mounted on a stainless steel plate for mounting on a standard electrical box See illustration and Base Mechanical Reference A4098 9733E is sealed against rear air flow entry and the electronics are EMI RFI shielded Dimensions are shown in the illustrations below 3 2 Rev 9 03 2021 Analog Heat Sensor A4098 9733E and Bases for Extended Exposure to High Humidity Heat Sensor Product Selection Chart Sensor 1 Heat Sensors 2 Sensor Bases options available Sensor Base Base for use with IDNet only input is automatically from output when a communications circuit occurs Base with wire connections for Remote Alarm Indicator or Unsupervised Relay Sensor Relay Base with connections for Remote Relay and connections for Alarm Indicator or Unsupervised Relay operation is programmable and can be operated from control panel Sensor Relay Base with connections for Remote Relay and connections for Alarm Indicator or Unsupervised Relay operation is programmable and can be operated from control panel Base with built in piezoelectric sounder power can be from 24 VDC or from compatible NAC sounder operation can be activated from the host control sounder output can be synchronized via or by the NAC if NAC powered options available for use only with models 4007ES 4010ES 4100ES alarm control panels Remote LED Alarm Indicator A4098 9822 Relay Remote Relay supervised Remote Alarm Indicator or Relay unsupervised Supervised Remote Relay Remote Alarm Indicator or Unsupervised Relay Remote LED Alarm Indicator A4098 9822 Relay quantity of sounder bases available coding on the same communications may vary with panel application availability of NAC power refer to control panel requirements Relay mounts remotely or in base box same size as A4098 9822 3 Accessories use with A4098 9791E base Relay mounts remote or in base box use with A4098 9780E base Requirements octagonal or 4 square box 1 depth or single gang box minimum depth octagonal or 4 square box Box depth requirements on total wire count and wire refer to accessories list below reference Requirements Mounting requires 4 or 4 square box 1 depth Mounting requires 4 octagonal 2 deep with 1 extension gang box 1 minimum depth octagonal box 2 deep with 1 extension ring Red LED Alarm Indicator on single gang steel plate tracks base led status activates when base is on steady indicating local alarm or trouble mounts only in base electrical box Plate required for some mounting 6 162 mm diameter 6.4 deep use with bases A4098 9789E and with each base can also be for cosmetic retrofitting to existing 6 diameter base product for surface or semi flush 4 square box and for mounted 4 octagonal box to publication A4098 Detectors Sensors and Bases Application Manual 574 709AC for additional information 3 Rev 9 03 2021 Analog Heat Sensor A4098 9733E and Bases for Extended Exposure to High Humidity