Visual Nurse Call 4000 Single Status Station Cornell DS-110 Duty Station offers immediate of any call on the system via tone and red LED on a status 4000 system. The DS-110 Duty Station has a manual high or low tone switch that is provided for an audible alert to staff. red LED indication with pulsing tone. The satin finish stainless steel faceplate with silk- designations may be flush mounted on a standard outlet with single-gang plaster ring, or surface mounted on a 5748 or equivalent. Field wiring terminations are pigtailed. Specifications: The duty station shall be CORNELL Model DS-110. Incoming calls shall be indicated by a (steady) red LED indicator and pulsing tone. The station have a manual switch for High-Low volume. The station shall fit on a standard single gang ring or Wiremold 5748 surface box or equal. Minimum depth shall be 1 Visual indicators be LED Incandescent lamps not accepted. Terminations for field wiring shall be pigtailed. Information: Power Requirements: 24VDC Operating Environment: 50-120 Indoor Non-condensing Physical Faceplate Dimensions: 4 x 2 (1 Gang) Mounting: Single-Gang back box with 1 minimum depth Wiring: Terminations are Pigtailed in 1-6 gang sizes: are only UL Listed in the 1 gang size