DSC FSB 210 IM EN NA

File Preview
File Preview
Click below to download for free

File Data

Name dsc-fsb-210-im-en-na-4627530819.pdf
Type PDF
Size 1.23 MB
Downloads

Text Preview

FSB 210 Series Smoke Detector and Operating Instructions this instruction sheet thoroughly before installation and use of the FSB 210 Series Smoke Detector Installation Sheet must be used in conjunction with the appropriate Alarm Controller Installation Manual magnet here T Marks Panel Compatibility smoke detectors are addressable system detec that are only for use with DSC fire and security con panels equipped with the compatible interface The smoke detectors cannot be used with a standard smoke detector interface Any standard 2 wire detector including the DSC FSA Series will not on an addressable circuit The FSB 210 series and FSA Series are not compatible interchangeable or addressable interfaces have a proprietary power and system Voltage ratings are not indicative of The current rating is provided for circuit calculations only Please refer to the control panel for details on the installation of addressable detectors are compatible with the following con units PC5010 PC5015 PC5020 PC5020CF v2 x with PC5100 module Maximum 32 detectors can be PC4010 PC4010CF PC4020 PC4020CF v3 x Maximum detectors can be installed every 7 to 8 seconds the unit tests for a or heat alarm condition During this sequence the also performs self diagnostics and checks for faults normal operation the LED will flash every 50 seconds Alarm smoke detector has a nominal fixed alarm sensitivity to the Specifications section on the back page and will go into alarm when the signal level exceeds the threshold and send the alarm signal to the control During an alarm the LED will flash every second Drift Compensation detector automatically compensates for long term induced changes to maintain a constant sensitivity When the drift compensation has its high or low limit of adjustment the detector go into the trouble state Alarm heat detector will go into alarm when the heat signal exceeds the heat alarm threshold 135 and the alarm signal to the control panel During an the LED will flash every second Indications in Production Range Smoke Heat Power Trouble Fault Trouble Test Failed 1 50s 1 1s Instructions Smoke Detector Placement smooth ceilings detectors be spaced 9.1m 30ft as a guide Other spac may be required depend on ceiling height air the presence of uninsulated ceilings Consult National Fire Code NFPA 72 Chap 11 or other appropriate standards for instal recommendations Do NOT locate smoke detectors at the top of peaked or ceilings the dead air space in these locations may the unit from detecting smoke Avoid areas with air flow near doors fans or windows Rapid movement around the detector may prevent smoke entering the unit Do NOT locate detectors in areas of high humidity Do NOT locate detectors in areas where the temperature above 38 100 or falls below 5 41 Smoke detectors in accordance with NFPA 72 11 detectors shall be installed outside each sleeping area in the immediate vicinity of the and on each additional story of the family liv unit including basements and excluding crawl spaces unfinished attics In new construction a smoke also shall be installed in each sleeping room Mount Smoke Detector backplate on standard octagonal electrical box the screws provided Power supply must be from a UL Listed control unit Install wir in accordance with the national and local codes Wiring Holes to the connection dia in this section Before the unit prepare wires from the electrical for connection the wires not be frayed or bent If power connec are reversed the unit not operate The unit is against damage incorrect wiring wiring is completed the wiring and cor any errors before apply power to the unit When the wiring has been reviewed neatly insert the wires into the elec box and secure the unit to the mounting plate This equipment should be installed in accordance the National Fire Protection Association Standard 72 Fire Protection Association Batterymarch Park MA 02269 Cover dust cover is intended to protect the smoke detector dust and dirt entry while the unit is not in service The dust cover protects the unit ONLY when it not in service Remove the dust cover before use Enrollment serial number located on the back of the device must enrolled into the alarm control panel via Installer Pro cid 1 8 Installer Code This procedure is out for Power panels in the PC5100 Installation Manual for the PC4010 4020 v3 x in the control panel Instal Manual Connect only DSC addressable series to the addressable loop connections Connec of any other type of device will impair operation other than addressable series devices which power to operate must be powered separately NOT use looped wire under terminals for system Break the wire run to provide supervision connections Mounting Installation the detector on to the base plate using the and base plate alignment marks Press the gently in place while rotating the detector clock until the detector snaps into place Remove the side from the locking tab to lock in place optional If the side tab removed to lock the depress a small flat blade and rotate detector counter marks Remove detector Test Unit Program the Panel for Smoke Test Refer to the Alarm Panel Installation Manual for details If the detector is in one of the following states test is initiated it will not enter an alarm state Compensation trouble Failure of heat or smoke detector Other internal faults that could prevent a smoke or alarm Use the FSD 100 meter to read the trouble status after Refer to the FSD 100 User Guide for details Place the meter close to the LED until it begins to every 2 seconds Then hold the meter on the oppo side of the LED and read the message The detector send out a test message 7 times in a 2 second inter until the LED stops flashing Compensation Reset replacement of the smoke sensor or other may change the background signal noise of the this requires the drift compensation be reset trouble is one of the faults indicated when LED indicator is OFF Remove power from the unit then press and hold the button for 30 seconds to power down unit Power up unit while pressing the test button The LED flash when 5 seconds has elapsed Release the button within 1 second after the fifth LED flash The LED will flash every 8 seconds for 1 minute the detector stops flashing test the detector to normal operation A good plan emphasizes a quick escape Do not inves first or attempt to fight the fire and do not to rescue belongings or valuables as this up time Once outside do not re enter the pre wait for the Fire Department Write the plan down and rehearse it frequently so if emergency occurs everyone will know what to do the plan as conditions change for example there are more fewer employees or if there are to the home building Make sure your fire warning system is operational by weekly tests If you are unsure about sys operation contact your smoke detector installer dealer DSC recommends that you contact your local Fire and request further information on fire and escape planning If available have your fire prevention officer conduct a fire safety recommends regular testing of Smoke Detectors to correct operation Contact your Installer or Dealer servicing and testing smoke detector is designed to require minimum If the case becomes dusty vacuum with a brush

Related Files