DSC PC1616 PC1832 PC1864 - Quick Installation Manual - Eng

File Preview
File Preview
Click below to download for free

Text Preview

PC1616 PC1832 PC1864 STANDARD INSTALLATION GUIDE Installation Guide provides the basic installation wiring and programming information required to program the PowerSeries PC1616 and PC1864 control panels This guide shall be used in conjunction with the PowerSeries PC1616 1832 1864 Reference Manual can be obtained from your local dealer or downloaded from the DSC web site at www dsc com All necessary information required to meet UL Listing requirements is contained in this document the complete guide then work through each step as indicated Of THE BOX 1 cid 84 1 cid 84 1 cid 84 1 cid 84 2 cid 84 1 cid 84 4 cid 84 16 cid 84 1 cid 84 1 cid 84 1 cid 84 1 cid 84 Module guide manual Label Door Plug Resistors Resistors Resistors Resistors Kit Zones 2 keypad zones Zones 1xPC5108 7xPC5108 PGM Outputs 1 50mA 2 300mA 1 50mA 2 300mA 1 3 4 50mA 2 300mA Expansion PC5208 mA PC5204 PC5208 mA PC5204 PC5208 mA PC5204 Zones Zone Support cid 23 Codes Buffer Master Codes Master Codes Master Codes Range 0 32 Max 93 R H Supply 16.5VAC 40VA 60Hz Draw Panel 110mA nom Output 11.1 12.6VDC 550mA Output 11.1 12.6VDC 700mA Events Events Events Required Required 7Ah 14AHr 7Ah 14AHr 7Ah 14AHr Output mA cont mA cont mA cont DEVICES Backward compatible with all PowerSeries keypads Keypad 150mA max Keypad 150mA max LED Keypad 150mA max LED Keypad 150mA max LED Keypad 150mA max Fixed Message LCD Keypad 85mA max 8 zone LED Keypad 100mA max 222x298x78mm 11.3x11.7x3.0in 213x235x78mm 8.4x9.25x3.0in to the reference manual for alternate control cabinets TL 250 TL300 275 350mA 2 wire Interface 40mA plus devices to 170mA max Wireless Receiver 125mA Wireless Receiver 125mA Zone Expander 30mA Power Supply with 4 Programmable Outputs 30mA Low Current Programmable Output Module 50mA Printer DVAC Module 65mA Bi Directional RS232 Module Not UL Listed 65mA Telephone Interface Module 130mA to the reference manual for additional devices in Accordance with ANSI SIA CP 01 2000 SIA FAR 9 0 0 7 1 0 9 R0 0 2 February 2006 Digital Security Controls in Canada the installation by mounting the cabinet in a dry protected area with access to unswitched AC power Hardware in the sequence indicated below Do NOT apply power until installation is complete Installation All wiring entry points are designated by arrows All circuits are classified UL power limited except for the battery leads 1 4 6.4mm separation must be maintained at all points between power limited and non power limited wiring and KEYBUS Wiring 4 wire KEYBUS red black yellow and green is the communication connection between the control panel and all modules The 4 KEY terminals of all modules must be connected to the 4 KEYBUS terminals of the main control panel following rules must be followed when wiring the Keybus 46 M 46 M 152 M 152 M Minimum 22 AWG wire maximum 18 AWG 2 wire twisted pre NOT use shielded wire Modules can be home run connected in series or can be T provided that the maximum wire distance from the control to any module does not exceed 1,000 feet 305m more than 3,000 feet 915m of wire can be used in total Zone Wiring can be wired for Normally Open Normally Closed Contacts Single end of line SEOL resistors or Double End of Line resistors Observe the following guidelines UL Listed Installations use SEOL or DEOL only Minimum 22 AWG wire maximum 18 AWG NOT use shielded wire Wire run resistance shall not exceed 100 Refer to the chart 001 004 Selects Zone Definition 013 Opt 1 Selects Normally Closed or EOL resistors 013 Opt 2 Selects Single EOL or Double EOL resis Status Resistance 0 shorted wire loop 5600 contact closed infinite broken wire open 11,200 contact open Status Bell Wiring terminals supply 700mA of current at 12VDC for commercial and 11.1 12.6 VDC for residential installations e g DSC WULF To comply with NFPA 72 Temporal Three Pattern Section 013 Opt 8 ON Bell output is supervised and power limited If unused connect a resistor across Bell and Bell to prevent the panel from dis a trouble See cid 52 2 max Polarit Bell output is current lim by 2A PTC Steady Pulsed and Tem Three Pattern alarms are Installation Cont Board Off Insert Stand off into cabinet mounting hole in the desired location Snap in place Position circuit board mounting holes over standoffs Press firmly on board to snap in place 16.5VDC 40VA 1640U II Transformer Do not connect to receptacle by a switch V 50 Hz International America Only LIMITED Tie not supplied recommended Voltage Disconnect AC Power telephone lines before servicing AC BELL BELL BLK YEL GRN PGM3 PGM4 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8 R 1 TIP T 1 Section 9 ground wiring details 7 AHr 7 AHr LIMITED Model BD7 12 equivalent Time min connections may result in PTC failure or improper operation wiring and ensure connections are correct before applying power connection of batteries may result in battery rupture or Fire Hazard NOT allow metal objects to connect the Positive and Negative Terminals that batteries are connected with correct polarity Red to Black to to comply with this may result in battery rupture and or Fire Hazard circuits are classified for UL Installations as power limited Class II power limited for battery leads which are not power limited NOT route any wiring over circuit boards Maintain at least 1 25.4mm separation minimum of 1 4 6.4mm separation must be maintained at all points between limited wiring and all other non power limited wiring corresponding Section NumberText for wiring details equipment Alarm Controller PC1616 1832 1864 shall be installed and used within an environment that provides the pollution degree max 2 and overvoltages category II NON HAZARDOUS LOCATIONS indoor only The equipment is FIXED and PERMANENTLY CONNECTED and is designed to be installed by service persons only service person is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task and of measures to minimize the risks to that person or other persons connection to the mains supply must be made as per the local authorities rules and regulations In the UK as per BS6701 An appropriate disconnect devic

Related Files