DSC Two Wire Smoke PC1616 1832 1864 V4 2
File Preview
Click below to download for free
Click below to download for free
File Data
Name | dsc-two-wire-smoke-pc1616-1832-1864-v4-2-6710295834.pdf |
---|---|
Type | |
Size | 589.08 KB |
Downloads |
Text Preview
Notes Two Wire Smoke Detectors PC1616 1832 1864 V4.2 SERIES PC1616 1832 1864 V4.2 smoke detectors use PGM2 of the main control panel and therefore do not take up a zone two wire smoke detectors is a three step process the PGM2 for two wire smoke support Wire the two wire smoke detector Sections Output Programming 1 Program PGM2 Section 009 program PGM2 as data 04 two wire smoke support 2 Wiring Two wire Smoke Detectors the two wire smoke detector to Aux and PGM2 Connect additional two wire smoke daisy chained from the previous one At the last smoke detector connect a 2.2K Ohm resistor the and terminals Tips Do not connect heat detectors to PGM2 They must be connected to a zone input To reset two smoke detectors press 7 2 or the RESET function key The panel will remove from PGM2 for five 5 seconds Test an alarm on a two wire smoke detector Verify the siren activates and the panel reports the two wire or auxiliary input alarm found in Section 329 Page 61