Edwards 156G Series Installation Instructions
File Preview
Click below to download for free
Click below to download for free
File Data
Name | edwards-156g-series-installation-instructions-6940123857.pdf |
---|---|
Type | |
Size | 637.69 KB |
Downloads |
Text Preview
Installation Instructions for the Number 156 Monitor Bell Edwards Catalog 156 Monitor Bells are insulated grounded bells featuring a concealed plunger and a corrosion re gray finish The grounding strap may be removed if not For outdoor applications the weatherproof gasket pro should be installed No MODELS Rating 8 10VAC 8 10VAC 8 10VAC MODELS No Rating 8 10VAC Bell gong size is denoted by suffix number For example has a six inch gong Canadian models provided with three inch gongs not apply power to the bell until installation has completed grounding is not required remove the grounding strap the back of the bell as follows See Figure 1 Remove the 6 32 x 1 4 pan head screw securing the strap strap Remove the adjacent terminal screw and remove the Replace the terminal screw removed in step 1b Replace the pan head screw removed in Step 1a with 6 32 x 3 8 nylon hex head screw supplied For use in outdoor applications install the weatherproof on the back of the bell Connect the bell to an appropriate AC or DC power source the terminal screws on the back of the bell Mount the bell to a flat surface using hardware appropriate the application Apply power and test the bell to ensure that it operates disconnect all power before servicing or bell Examine the bell periodically for accumulation of dirt and as necessary 1 CT 203 699 3000 FAX 203 699 3075 ISSUE 2 1996