Edwards AE Bulletin, E-FSA Panel Modem Connections
File Preview
Click below to download for free
Click below to download for free
File Data
Name | edwards-ae-bulletin-e-fsa-panel-modem-connections-4186975032.pdf |
---|---|
Type | |
Size | 757.80 KB |
Downloads |
Text Preview
040710 April 7 2010 E FSA Fire Alarm Panel Modem Connection When calling into an E FSA fire panel SA DACT dialer card remotely with the FSA CU utility program and a modem it is possible for the connection to drop immediately it was established If the card is configured for Single or Dual Line dialer mode under certain once the connection is made the panel will go into programming mode which will cause the panel to want to send a CID contact ID string to a central monitoring station In to do this the panel will hang up on the incoming call to dial out To prevent the panel from sending the CID for program mode and therefore possibly up on an incoming call you must go into the Event section of the CU and change the Mode Telco Account information to None Note You may have to download directly laptop to panel using SA 232 or SA ETH the first time in order to make these changes From panel keypad you can also go to Program Advance Program Panel Events Program Event Notification Dialer change to None Signaling Part of Fire S 800 336 4206 Web www edwardssignaling com 41 Woodford Ave Plainville CT 06062 E mail signaling techsupport ge com 1 of 1