Faraday HBC-1 OPTIONAL BATTERY CHARGER

File Preview
File Preview
Click below to download for free

File Data

Name faraday-hbc-1-optional-battery-charger-9134765028.pdf
Type PDF
Size 670.22 KB
Downloads

Text Preview

INSTALLATION INSTRUCTIONS AND WIRING FOR NO HBC 1 OPTIONAL BATTERY CHARGER HBC 1 Optional Battery Charger is an optional module for the MPC 7000 Fire Alarm System Control The HBC 1 provides the ability to charge lead acid batteries with AH ratings of 38 100 AHs One may be mounted in the MPC 7000 enclosure where the internally mounted batteries would go SUPPLIED 1 Screws 6 32 x Spacers Cable Assembly Sheet Battery Charger is to be done by qualified personnel have thoroughly read and understood this sheet 2 Disconnect BATTERY and AC prior to working on 3 Mount the spacers P N 375 444841 on the four just below the Main Termination Board mount the Optional Battery Charger with four P N 906 220604 as shown 4 Connect cable assembly P N 555 148970 from on the HBC 1 to J13 on the main termination 5 Mount batteries in BE 1 Battery Enclosure The must be in the same room as the MPC Fire Alarm Control Unit and connect to it with Attach conduit and run wires as required 6 Make sure field wiring is free and clear of opens 7 Apply power to system Then connect batteries to shorts system 8 Check for proper operation of functions operating current charging current voltage max during recharge Amps Nominal to be installed in accordance with all local codes Mounting J13 on the Termination Board 315 447362FA 1 1 OF 1 Wiring