Two Wire Smoke Detectors Power632 PC5010 Power832 PC5020 Power864 smoke detectors use PGM2 of the main control panel and therefore do not take up a two wire smoke detectors is a three step process Program the PGM2 for two wire smoke support Wire the two wire smoke detector Remove the jumper J1 or CON1 Sections Output Programming 1 Program PGM2 Section 009 program PGM2 as data 04 two wire smoke support 2 Wiring Two wire Smoke Detectors the two wire smoke detector to Aux and PGM2 Connect additional two wire detectors daisy chained from the previous one At the last smoke detector connect a resistor across the and terminals 3 Remove the Jumper J1 or CON1 is a jumper marked J1 or CON1 This must be removed if two wire smoke detectors are used The panel will show a fire trouble if the jumper is not removed J1 or CON1 is not present on the panel the version of control panel does not two wire smoke detectors Tips Do not connect heat detectors to PGM2 They must be connected to a zone input To reset two smoke detectors press 7 2 or the RESET function key The panel will power from PGM2 for five 5 seconds Test an alarm on a two wire smoke detector Verify the siren activates and the panel reports two wire smoke or auxiliary input alarm found in Section 329