Simplex 4001-9810 Alarm Relay Module

File Preview
File Preview
Click below to download for free

File Data

Name simplex-4001-9810-alarm-relay-module-0246375918.pdf
Type PDF
Size 810.30 KB
Downloads

Text Preview

s Simplex Alarm Relay Module alarm relay module is an accessory rated at 2A When used the relays work as follows 4001 fire alarm systems It contains four SPDT Relay Kl energizes when there is an alarm on Zone 1 Relay K2 energizes when there is an alarm on Zone 2 Relay K3 energizes when there is an alarm on Zone 3 Relay K4 energizes when there is an alarm on Zone 4 module may be mounted two ways If the 4001 9804 suppressor boards are NOT being used zone disconnect or 9807 transient module may be the control panel as shown in Figure 1 The module may be mounted externally a six gang box supplied by others as in Figure 2 mounting six gang trim plate before installation board in the control panel remove the relay board mounting bracket MOUNTING FROM MOUNT BOARD PANEL 1 1989 Simplex Recorder Co Gardner Mass 01441 0001 U S A Manuals Online the alarm relay module to the panel as follows refer to Figure 3 Connect the module ANN1 wire TBl 1 TE33 4 ANN1 the module ANN2 wire TBl 2 the module ANN3 wire Tel 3 the module ANN4 wire TBl 4 TB3 5 ANN2 TB3 8 ANN3 TB3 7 ANN4 Connect the module AUX wire TB2 8 to TB2 4 AUX module AUX wire TB2 7 to Tf35 8 NO of AUX 1 Connect a wire from the panel RMT to TB5 7 C of AUXl Refer to the system wiring diagrams 841810 information on external device the alarm relay module Refer to the 4001 9403 and 9404 Operating And details on panel configuration when using an Pub No FA4 31 001 relay module RELAY BRACKET ASSEMBLY HEAD SCREWS 4 2 11 89 Manuals Online

Related Files