System Sensor M500M EngSpec

File Preview
File Preview
Click below to download for free

File Data

Name system-sensor-m500m-engspec-2630814975.pdf
Type PDF
Size 620.56 KB
Downloads

Text Preview

Product Monitor Module and Engineering Specifications monitor module shall be a System Sensor model number M500M Intelligent monitor shall connect one supervised initiating device circuit IDC or zone of conventional alarm devices any normally open dry contact device to the fire alarm control panel signaling circuit SLC Loop Module shall have ability to uniquely signal an open circuit modules shall provide address setting means on the module using rotary switches Because the possibility of installation error systems that use binary jumpers or DIP switches to set the address are not acceptable The modules shall also store an internal identifying code the control panel shall use to identify the type of module Systems that require a special to set the module address including temporary connection at the panel are labor and not acceptable Each module occupies any one of at least 99 possible addresses the SLC loop It responds to regular polls from the system and reports its type and status module shall have an LED that is controlled by the panel to indicate module status Coded transmitted from the panel can cause the LED to blink latch on or latch off Refer to the panel technical documentation for module LED status operation module shall mount in a standard 4 inch square 2 1 8 deep electrical box or to a surface backbox The IDC zone shall be wired for Class A Style D or Class B Style B The module will use SEMS screws for easy wiring Wiring terminals shall be easily for troubleshooting without removal from electrical box UL 864 Control Units and Accessories for Fire Alarm Systems Agency Standards ULC S527 Control Units for Fire Alarm Systems ANSI NFPA 72 National Fire Alarm Code 2009

Related Files