System Sensor m501m-installation

File Preview
File Preview
Click below to download for free

File Data

Name system-sensor-m501m-installation-6019358274.pdf
Type PDF
Size 646.26 KB
Downloads

Text Preview

INSTALLATION AND MAINTENANCE INSTRUCTIONS SENSOR Division of Pittway 3825 Ohio Avenue St Charles Illinois 60174 FAX 630 377 6495 Monitor Module Descritption M501M monitor module provides a two wire Styles A B initiating circuit for normally open contact fire alarm supervisory devices Set the address on the module per job drawings Place the module in its desired mounting position Perform step one two and three for all modules M501M is small enough to fit inside a single gang junc box behind the monitored device The small size and weight allow it to be installed without rigid mounting Figure 1 1 not connect circuit wiring to the control unit or mod or apply power to any portion of the system until after circuit test has been performed All wiring must conform to applicable local codes and regulations Install module wiring in accordance with the job draw and appropriate wiring diagram Figure 2 length 6 min 2 Typical 2 wire styles A and B initiating circuit configuration of an M501M monitor module LISTED PANEL CD THE INITIATING CIRCUIT IS LIMITED TO 230 AMP NOM DETECTION LOOP PROVIDES FOLLOWING SERVICES AUTOMATIC MANUAL SERVICE N O CONTACT DEVICES SUPERVISION WITH CONTACT DEVICES DO NOT MIX SERVICES INITIATING CIRCUIT LINE LENGTH 2500 RESISTANCE 40 OHMS A COMPATIBLE UL LISTED PANEL EOL Manuals Online System Sensor 1996

Related Files