Note The switch rating is 3 amps 30 Volts AC DC Denotes solder connection BG 10L BG 10WP HR 10 AR 10F Series Pull Station Installation Drawing 15486 Rev F 9 04 96 ECN 96 323 contact for functions control panel loop output control panel loop output next device or ELR control panel loop output next device or ELR terminal block tests or to circuit operated control panel loop output next device or ELR next device or ELR BG 10 Series Pull Stations are non coded dual action normally open manual pull stations with the following options with AUX switch BG 10L with key for reset BG 10P T with key for presignal or test BG 10N without terminal BG 10WP BG 10 enclosed in a weatherproof backbox HR 10 Halon Release with wiring the same as the BG 10 Agent Release with wiring the same as the BG 10 Series Operation the dual action door is pushed in and the handle pulled down the N O push type switches will close The handle cannot restored to its normal position until the station is manually reset by unscrewing the hex screw and pivoting the case away from the backplate When the handle is restored return the case to its normal position and secure with the screw Note The BG 10L utilizes a mechanical key instead of a hex screw The microswitch of the BG 10P T is activated rotating a key clockwise The key cannot be removed while in this position Clintonville Road Northford CT 06472 203 484 7161 203 484 7118