Fire-Lite CP355 Plug-in Addressable Ionization Sensor Installation and Maintenance Instructions

File Preview
File Preview
Click below to download for free

Text Preview

CP355 Plug in Addressable Ionization Sensor and Maintenance Instructions DESCRIPTION sensor must be installed in compliance with the control panel system installation manual The installation must meet the requirements of the Having Jurisdiction AHJ Sensors offer maximum performance when installed in compliance with the National Fire Protection Association see NFPA 72 CP355 intelligent ionization sensor uses a state of the art sensing chamber This sensor is designed to provide open area protection and is intend for use with compatible control panels only LEDs on each sensor light to provide a local visible sensor indication Remote LED annunciator capability is available as an optional accessory No RA400Z CP355 requires compatible addressable communications to function properly Connect this sensor to listed compatible control panels Voltage Range Avg Standby Current Alarm Current LED on Humidity Range Temperature Range to 32 VDC 24 VDC one communication every 5 sec with LED blink enabled mA 24 VDC to 93 Relative Humidity noncondensing to 49 32 to 120 inches 43 mm installed in B350LP Base inches 155 mm installed in B350LP Base oz 102 g ANNUNCIATOR Do not loop wire under terminal 1 or 2 wire run to provide supervision of connections recommends spacing sensors in compliance with 72 In low air flow applications with smooth ceilings sensors 30 feet apart For specific information regard sensor spacing placement and special applications refer NFPA 72 or the System Smoke Detector Application Guide from Fire GUIDE wiring must be installed in compliance with the National Code applicable local codes and any special of the Authority Having Jurisdiction Proper wire should be used The installation wires should be color to limit wiring mistakes and ease system trouble shoot Improper connections will prevent a system from respond properly in the event of a fire power from the communication line before installing sensors Wire the sensor base supplied separately per the wiring diagram see Figure 1 Set the desired address on the sensor address switches see Figure 2 Install the sensor into the sensor base Push the sensor into the base while turning it clockwise to secure it in place After all sensors have been installed apply power to the control unit and activate the communication line Test the sensor s as described in the TESTING section of this manual A OPTIONAL WIRING 1 covers provide limited protection against airborne dust particles during shipping Dust covers must be removed before the sensors can sense Remove sensors prior to heavy remodeling or construction Tamper Resistance CP355 includes a tamper resistant capability that prevents its removal from the bracket the use of a tool Refer to the base manual for details on making use of this capability After all sensors have been installed apply power to the system See Figure 3 Test the sensor by positioning a test magnet against the sensor plastic in the test area The alarm level should be recognized at the panel and the LED controlled by command from the panel Reset the sensor by communication command from the panel Stop 0 0 2 One Fire Place Northford CT 06472 1653 203 484 7161 cleaning notify the proper authorities that the system is undergo maintenance and will be temporarily out of service Disable the system prevent unwanted alarms Remove the sensor to be cleaned from the system Remove the sensor cover Press firmly on each of the four removal that hold the cover in place Vacuum the outside of the screen carefully If further cleaning is continue with Step 4 otherwise skip to Step 5 Use clean compressed air to remove dust and debris from the sens chamber Replace the cover using the LEDs to align the cover and then gently it until it locks into place Reinstall the detector Test the detector as described in TESTING Reconnect disabled circuits Notify the proper authorities that the system is back on line Screen 4 Cleaning must be tested after installation and following periodic mainte However before testing notify the proper authorities that the detector system is undergoing maintenance and the system will be out of service Disable the zone or system undergoing mainte to prevent unwanted alarms methods must satisfy the Authority Having Jurisdiction AHJ offer maximum performance when tested and maintained in com with NFPA 72 the sensors as follows Functional Magnet Test P N M02 04 01 or M02 09 00 sensor can be functionally tested with a test magnet The test electronically simulates smoke in the sensing chamber testing sensor electronics and connections to the control panel Hold the test magnet in the magnet test area as shown in Figure 3 The sensor should alarm the panel LEDs on the sensor are controlled by the panel to indicate sen status Coded signals transmitted from the panel can cause the to blink latch on or latch off Refer to the control panel tech documentation for sensor LED status operation and expected to alarm Smoke Entry Aerosol Generator Gemini 501 GEMINI model 501 aerosol generator can be used for smoke entry Set the generator to represent 4 ft to 5 ft obscuration as in the GEMINI 501 manual Using the bowl shaped applica apply aerosol until the panel alarms sensor that fails any of these tests should be cleaned as described under and retested If the sensor fails after cleaning it must be testing is complete restore the system to the normal operation and the proper authorities that the system is back in operation Test Magnet Status Test Magnet 3 Test Magnet Positioning refer to insert for the Limitations of Fire Alarm Systems device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this must accept any interference received including interference that may cause undesired operation This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interfer will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Statement Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Fire

Related Files