Fire-Lite MS-9200UD & MS-9200UDE Remote Station Connection
File Preview
Click below to download for free
Click below to download for free
File Data
Name | fire-lite-ms-9200ud-ms-9200ude-remote-station-connection-1486970253.pdf |
---|---|
Type | |
Size | 755.14 KB |
Downloads |
Text Preview
Central Station Remote Station to FACP Dry Contacts Installation Document 53046 Rev A 8 21 06 ECN 06 582 Product Installation Document outlines the connection of a UL 864 Listed Central Station Remote Station to Fire Lite Fire Alarm Control Panel dry contacts The FACP contacts must be supervised by the Station Remote Station Transmitter module using End of Line Resistors ELRs with a value determined the Transmitter manufacturer Power is also provided by the Central Station Remote Station Transmitter Refer to the Central Station Remote Station Transmitter manufacturer s manual for details Central Station Remote Station Transmitter Module Input Zone Triggers FACP Relay Relay Relay The Trouble Relay is a fail safe relay power applied to the FACP and no in the panel the contacts should be in condition indicated in the illustration detailed information on specific Fire Lite FACPs refer to the appropriate panel manual as listed below MS 9200UD MS 9200UDLS MS 9600 MS 9050UD MS 4 MS 5210UD P N 51906 P N 52750 P N 51335 P N 52413 P N 51512 P N 50193 requires use of optional NAC REM module for supervisory relay