Fire-Lite SD365R, SD365R-IV Intelligent Photoelectric Smoke Sensors

File Preview
File Preview
Click below to download for free

Text Preview

INSTALLATION AND MAINTENANCE INSTRUCTIONS and SD365R IV Photoelectric Smoke Sensor Remote Test Capability in Duct Applications Voltage Range Current 24 VDC Alarm Current Current Humidity Range Temperature Range Velocity Load Rating refer to your isolator base module manual for isolator calculation instructions to 32 VDC uA one communication every 5 seconds with green LED blink on communication mA 24 VDC one communication every 5 seconds with red LED solid on mA 24 VDC one communication every 5 seconds with amber LED solid on to 93 Relative Humidity Non condensing to 122 0 to 50 4 to 158 20 to 70 in duct applications to 4000 ft min 0 to 1219.2 m min 51 mm installed in B300 6 Base 156 mm installed in B300 6 Base 4.1 104 mm installed in B501 Base oz 95 g FireLite Place CT 06472 203.484.7161 Test the sensor s as described in the TESTING section of this manual listed for Duct Applications sensor must be installed in compliance with the control panel system manual The installation must meet the requirements of the Au Having Jurisdiction AHJ Sensors offer maximum performance when in compliance with the National Fire Protection Association NFPA NFPA 72 DESCRIPTION SD365R and SD365R IV are plug in type smoke sensors that combines photoelectronic sensing chamber with addressable analog communications used in duct applications with a DNR W testing can be done remotely approved System Sen sor test accessories eliminating the need for a test The sensors transmit an analog representation of smoke density over a line to a control panel Rotary dial switches are provided for the sensor address 1 ROTARY ADDRESS SWITCHES 0 0 LEDs on the sensor are controlled by the panel to indicate sensor status output is provided for connection to an optional remote LED annunciator RA100Z Only System Sensor approved accessories may be used with the SD365R SD365R IV panels offer different features sets across different models As a re certain features of the photoelectric sensors may be available on some panels but not on others SD365R will support only LiteSpeed pro mode SD365R IV will support either LiteSpeed or CLIP Classic Loop Protocol mode The possible features available in the SD365R and if supported by the control panel are The sensor LEDs can operate in three ways off and blinking can be set to red green or amber This is controlled by the panel The remote output may be synchronized to the LED operation or con independent of the LEDs Devices are point addressable up to 159 addresses refer to the operation manual for the UL listed control panel for specific The SD365R and SD365R IV require compatible addressable com to function properly Connect these sensors to listed compatible panels only recommends spacing sensors in compliance with NFPA 72 In low air applications with smooth ceilings space sensors 30 feet apart 9.1 m specific information regarding sensor spacing placement and special ap refer to NFPA 72 or the System Smoke Detector Application Guide from Fire Lite Applications SD365R and SD365R IV are listed for use in ducts See Smoke Detectors Applications Guide HVAG53 for details on pendant applications NOTE SD365R and SD365R IV are also listed for use in DNR W duct smoke detectors GUIDE wiring must be installed in compliance with the National Electrical Code local codes and any special requirements of the Authority Having Proper wire gauges should be used The installation wires should color coded to limit wiring mistakes and ease system troubleshooting Im connections will prevent a system from responding properly in the of a fire power from the communication line before installing sensors Wire the sensor base supplied separately per the wiring diagram Figure 2 Set the desired address on the sensor address switches see Figure 1 Install the sensor into the sensor base Push the sensor into the base while it clockwise to secure it in place After all sensors have been installed apply power to the control panel and the communication line covers provide limited protection against airborne dust particles during Dust covers must be removed before the sensors can sense smoke sensors prior to heavy remodeling or construction 2 WIRING DIAGRAM Do not loop wire under 1 or 2 Break wire run to connections A OPTIONAL WIRING SD365R and SD365R IV include a tamper resistant capability that pre their removal from the base without the use of a tool Refer to the base for details on making use of this capability C0129 10 testing notify the proper authorities that the system is undergoing and will temporarily be out of service Disable the system to unwanted alarms sensors must be tested after installation and periodically thereafter Test methods must satisfy the Authority Having Jurisdiction AHJ Sensors maximum performance when tested and maintained in compliance with 72 sensor can be tested in the following ways Functional Magnet Test P N M02 04 01 or M02 09 00 Hold the test magnet in the magnet test area as shown in Figure 3 This sensor can be functionally tested with a test magnet The test magnet simulates smoke in the sensing chamber testing the sensor and connections to the control panel The sensor should alarm the panel Two LEDs on the sensor are controlled by the panel to indicate sensor Coded signals transmitted from the panel can cause the LEDs to latch on or latch off Refer to the control panel technical documen for sensor LED status operation and expected delay to alarm Smoke Entry Sensitivity readings are available through the FACP Refer to the manufac published instructions for proper use Additionally canned aerosol simulated smoke canned smoke agent may used for smoke entry testing of the smoke detector Tested and ap aerosol smoke products are removing the detector notify the proper authorities that the smoke system is undergoing maintenance and will be temporarily out of Disable the zone or system undergoing maintenance to prevent un alarms Remove the sensor to be cleaned from the system Remove the sensor cover by pressing firmly on each of the four removal that hold the cover in place Vacuum the screen carefully without removing it If further cleaning is continue with Step 4 otherwise skip to Step 7 Remove the chamber cover screen assembly by pulling it straight out Use a vacuum cleaner or compressed air to remove dust and debris from sensing chamber Reinstall the chamber cover screen assembly by sliding the edge over the chamber Turn until it is firmly in place Replace the cover using the LEDs to align the cover and then gently push it until it locks into place Reinstall the detector Test the detector as described in TESTING Reconnect disabled circuits Notify the proper authorities that the system is back on line NOTE REGARDING SMOKE DETECTOR GUARDS detectors are not to be used with detector guards unless the combina has been evaluated and found suitable for that purpose 3 FEATURES OF THE PHOTO DETECTOR 30S PURCHECK CENTURIAN SOLOA4 TRUTEST 2000 Alignment Notch When used properly the canned smoke agent will cause the smoke detec to go into alarm Refer to the manufacturer published instructions for use of the canned smoke agent 4 CLEANING THE PHOTO DETECTOR Test Marker C2021 01 aerosol simulated smoke canned smoke agent formulas will vary by Misuse or overuse of these products may have long

Related Files