Kidde 3101084-EN R006 FX-IDCWS Analog Dual Input Waterflow - Supervisory Module Installation Sheet

File Preview
File Preview
Click below to download for free

Text Preview

To install the module Verify that all field wiring is free of opens shorts and ground Make all wiring connections as shown in and Figure 3 Set the module address Refer to the panel technical reference for a list of valid addresses a screwdriver to adjust the two rotary switches on the front of module Set the TENS rotary switch 0 through 12 for the 10s 100s digit and the ONES rotary switch for the 0 through 9 For example device address 21 set TENS rotary switch to 2 set the ONES rotary switch to 1 see Figure 1 Mount the module on the electrical box using screws provided with Mount the wall plate on the module using the hardware shown in electrical box 2 1 Module address Insert screwdriver here 2 Module installation Analog Dual Input Supervisory Installation Sheet module is an analog addressable device used to connect normally waterflow alarm and supervisory initiating device circuits IDCs a control panel This module is designed for Class B circuit device address is set using the two rotary switches located on the of the module Two consecutive device addresses are required second device address is automatically assigned one number than the value set on the rotary switches module can operate in the following modes 1 Module operation type description latching delayed Configures the module for use only nonretarded waterflow alarm switches When NO input contact of an initiating device is closed an is sent to the control panel which after a 16 time delay generates an alarm signal Supervisory active nonlatching US marketplace active latching Canadian marketplace Configures the module for normally open contact initiating devices When the NO input of an initiating device is closed a supervisory is sent to the control panel and the supervisory is not latched at the module Configures the module for normally open dry initiating devices When the NO input contact of initiating device is closed a supervisory signal is to the control panel and the supervisory condition not latched at the module operation module provides a bicolor LED that shows its status Green LED flashes Red LED flashes and wire this device in accordance with applicable national and codes ordinances and regulations This module will not operate without electrical power As fires cause power interruption you should discuss further with your local fire protection specialist This module does not support conventional smoke detectors The module is shipped from the factory as an assembled unit it no user serviceable parts and should not be disassembled 2020 Carrier 2 3101084 EN REV 006 ISS 20OCT20 Cover plate plastite screws 2X Wall plate Screw Module Compatible electrical box the device as shown in Figure 3 Be sure to observe the polarity the wires This module does not support two wire smoke detectors All wiring is power limited and supervised Refer to the control panel technical reference manual for wiring line voltage fault impedance environment humidity temperature range electrical boxes size device circuit IDC resistor value circuit resistance circuit capacitance 3 Module wiring 20.6 V peak to peak k to 120 0 to 49 to 93 noncondensing at 32 to 140 to 60 American 4 inch square in 64 mm deep 2 gang box 4 in square box 1 1 2 in mm deep 14 16 or 18 AWG wire 2.5 1.5 or 0.75 mm2 Sizes 16 and AWG are preferred k P N EOL 47 25 per wire To next device From previous device Class A or Class B Class B Maximum 25 resistance per wire information contact information see www kidde esfire com Maximum 12 AWG wire minimum 18 AWG wire Maximum 10 VDC at 350 Typical normally open NO supervisory tamper switch Typical normally open NO waterflow switch k EOLR 2 3101084 EN REV 006 ISS 20OCT20

Related Files