Installation Wiring for N O Single and Pole Fire Alarm Stations Installation Sheet the glass rod after mounting on all catalog K 276 and models installations Fire alarm system components and wiring be installed in accordance with the local recognized of CAN ULC S524 C22.1 Canadian Electrical code Part Section 32 and in accordance with the local authorities jurisdiction installations Fire alarm system components and wiring be installed in accordance with NFPA 70 National Code NFPA 72 National Fire Alarm and Signaling and in accordance with the local authorities having 1 Double pole normally open N O switch contact for customer use 560 ohm resistor is to 270L model only the Fire Alarm Station in accordance with Figure 1 or 2 for the applicable catalog number ensure proper supervision of connections Do not use looped wires under terminals Break the wire Use both sides of the terminal screw as shown in 3 Do not twist wires together branching to be as shown in Figure 1 and Figure 2 numbers UL only UL only UL only Alarm 2 3102418 EN REV 01 ISS 27JUN16 2 Single pole normally open 560 ohm resistor is to 270L model only numbers 1110 UL only 1120 UL cUL 1110 UL only 1120 UL cUL UL cUL Alarm 3 Wire break example information contact information see www kiddelifesafety com 2016 Walter Kidde Portable Equipment Inc rights reserved 2 3102418 EN REV 01 ISS 27JUN16