INSTALLATION AND MAINTENANCE INSTRUCTIONS Interchange Way Vaughan Ontario L4K 5W3 905.660.4655 Fax 905.660.4113 Relay Control Module Operating Voltage Alarm Current Operating Current Resistance Range to 32 VDC LED on 1 communication every 5 seconds used to 120 0 to 49 to 93 Non condensing H x 4 W x 11 4 D Mounts to a 4 square by 21 8 deep box Electrical Box CB500 Barrier 1 CONTROLS AND INDICATORS INSTALLINg information is included as a quick reference installation guide Refer to control panel installation manual for detailed system information If the will be installed in an existing operational system inform the opera and local authority that the system will be temporarily out of service Dis power to the control panel before installing the modules This manual should be left with the owner user of this equipment DESCRIPTION MIX M500RAPA Relay Control Module is intended for use in intelligent systems where the individual address of each module is selected the built in rotary decade switches It allows a compatible control panel switch discrete contacts by code command The relay contains two iso sets of Form C contacts which operate as a DPDT switch and are rated accordance with the table in the manual Circuit connections to the relay are not supervised by the module The module also has a panel LED indicator REqUIREMENTS ensure proper operation these modules shall be connected to listed com system control panels only MIX M500RAPA mounts directly to 4 square electrical boxes see Fig 2A The box must have a minimum depth of 21 8 Surface mounted elec boxes SMB500 are available from Mircom All wiring must conform to applicable local codes ordinances and When using control modules in nonpower limited applications Mircom CB500 Module Barrier must be used to meet UL requirements for separation of power limited and nonpower limited terminals and wiring barrier must be inserted into a 4 junction box and the control must be placed into the barrier and attached to the junction box Fig 2A The power limited wiring must be placed into the isolated quadrant of module barrier Figure 2B Install module wiring in accordance with the job draw and appropriate wiring diagrams Set the address on the module per job drawings Secure module to electrical box supplied by installer shown in Figure 2A 2A MODULE MOUNTINg WITh BARRIER 2B CONTACT RATINgS RATINg VOLTAgE DESCRIPTION A A A A A A A A VDC VDC VDC VDC VAC VAC VAC VAC L R 20ms 0.75 relay switch contacts are shipped in the standby open state but may have transferred to the activated closed state during shipping To ensure that the contacts are in their correct state modules must be made to communicate with the panel before connecting circuits controlled by the module 3 RELAy MODULE WIRINg DIAgRAM NEXT MODULES TO LISTED COMPATIBLE PANELS ONLY PANEL OR DEVICE LINE CIRCUIT SLC VDC MAX PAIR RECOMMENDED COMMON 2 CLOSED 2 OPEN 2 COMMON 1 CLOSED 1 ANY WIRING TO TERMINALS 4 10 IS NONPOWER THE CB500 BARRIER IS REQUIRED THE CB500 A NONPOWER LIMITED LABEL WHICH MUST PLACED OVER THE POWER LIMITED TERMINAL ON THE NAMEPLATE LABEL OPEN 1 MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS ANY FAULT IN THE POWER SUPPLY IS TO THAT ZONE AND DOES NOT IN A FAULT IN A SEPARATE ZONE Mircom

Related Files