Mircom IIBPS602 BPS-602 NAC Power Extender Installation Guide (English)
File Preview
Click below to download for free
Click below to download for free
File Data
Name | mircom-iibps602-bps-602-nac-power-extender-installation-guide-english-4019285637.pdf |
---|---|
Type | |
Size | 1.29 MB |
Downloads |
Text Preview
BPS 602 Power Extender Guide Application Guide for additional information 042209 NAC Power Extender Mircom BPS 602 is an extremely cost effective 6.5 amp remote power supply battery charger It may be connected to 24 volt Fire Alarm Control Panel FACP Primary applications include Notification Appliance Circuit NAC such as and horns expansion support to meet ADA requirements It also provides auxiliary power to support system acces The unit delivers electronically regulated and filtered 24 volt power to Class B Style W X Y or Class A Style Z loop circuits Additionally a separate 1.0A auxiliary output for four 4 wire smoke detectors is available The 6.5 max alarm current can be divided between the four 4 outputs for powering NAC devices Each output is rated at 2.5 max and can be independently programmed for Steady Temporal Code 3 or Strobe Synchronization All outputs may programmed for Input to Output Follower Mode output will follow input An individual output of 4 amp is achieved paralleling 2 outputs In non alarm condition independent loop supervision for Class A Style Z and or Class B Style X Y FACP NAC circuits is provided In the event of a loop trouble the FACP will be notified via the steered input 1 or input 2 In addition there are common trouble output terminals NC C NO which are used to indicate general trouble A common trouble input is provided for optional NC normally closed devices to report trouble to the Two 2 FACP signaling outputs can be employed and directed to control supervision and power delivery to any of the four 4 outputs Agency Listings UL Listed Control Units and Accessories for Fire Systems UL 864 MEA NYC Department of Buildings Approved CSFM California State Fire Marshal Approved FM Factory Mutual Approved NFPA 72 Compliant Power input 120VAC 60 Hz 4 amp Two 2 Class A Style Z or two 2 Class B Style W X Y FACP inputs Two 2 NC dry contact trigger inputs 24VDC 6.5 amp max total alarm current 2.5 amp max current per output Separate 1.0 amp auxiliary output Two 2 outputs may be paralleled for more power on an Programmable supervised indicating circuit outputs Four 4 Class B Style W X Y or Two 2 Class A Style Z or One 1 Class A Style Z and Two 2 Class B Style W X Y see 02 Application Guide Thermal and short circuit protection with auto reset Backup Charging voltage is 26.2 26.4VDC Built in charger for sealed lead acid or gel type batteries Automatic switchover to stand by battery when AC Fails Zero voltage drop when switching over to battery backup AC fail supervision form contact 1 amp 28VDC Factory set for 30 seconds with optional 2.5 to 3 hour delay setting field selectable circuit see 02 Application Guide cont Instant local AC trouble reporting relay form contact 1 amp 28VDC Battery presence and low battery supervision form contact 1 amp 28VDC Indicators Input and output status LED indicators Features 2 wire horn strobe Sync mode allows audible notification appliances horns to be silenced while visual notification appliances strobes continue to operate Sync protocols include Potter Amseco Faraday Gentex System Sensor and CooperWheelock Temporal Code 3 Steady Mode Input to Output Follower Mode maintains synchronization of notification appliances circuit Compatible with 12VDC or 24VDC fire panels Output loop supervision steered to input 1 or input 2 Signal circuit trouble memory helps identify Common trouble input and output for external trouble signals tie in Ground fault detection Unit includes power supply red enclosure cam lock and battery leads Dimensions approx H x W x D 15.5 x 12 x 4.5 393.7mm x 304.8mm x 114.3mm loop problems To reduce the risk of fire or electric shock do not expose the unit to rain or moisture installation should be made by qualified service personnel and should conform to all local codes 2 Input Supply Specifications 60Hz 4 amp 4 regulated supervised NAC output circuits 24VDC 2.5 amp maximum current 1 aux special application 24VDC power output circuit 1 amp non supervised output current must not exceed current 6.5 amp in Alarm Condition two 2 12VDC 7AH two 2 12VDC 12AH or two 2 12VDC 40AH connected in series Current Resistor end of line fault maximum impedance 2200 ohm ohm Specifications Time Total Amp Minutes Alarm Output Current Aux Output Batteries two 2 12VDC batteries in series amp Unit is equipped with 1 amp max auxiliary output will remain battery backed up during power For loads connected to please refer to battery Specifications above for ratings When are connected to output during alarm condition the remaining outputs may not exceed 6.5 amp alarm current example AUX 1 amp outputs up to 5.5 amp amp 5 minutes amp 5 minutes amp 5 minutes Hours Hours Hours Instructions N 1 3 3 4 4 5 6 6 Mode Selection Table Identification Table Status Indication Table review Guide for BPS 602 BPS 802 BPS 1002 Supply Specifications Specifications Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure keyholes over the two upper screws level and secure Mark the position of the lower two holes Remove the Drill the lower holes and install two fasteners Place the enclosure upper keyholes over the two upper Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pg 12 enclosure to earth ground Fig 1 pg 3 Small terminal block wire gauges range from AWG to 24 AWG all others range from 14 AWG to 24 AWG methods shall be in accordance with the National Electrical Code NFPA 70 NFPA 72 ANSI and with all local and authorities having jurisdiction is intended for indoor dry use only Output Programming Selection Table Mount unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the Connect the line L and neutral N terminals to a separate unswitched AC circuit 120VAC 60Hz Measure output voltage before connecting devices This helps avoiding potential damage Connect battery to the terminals marked BAT on the Power Supply Board battery leads included Use two 2 12VDC batteries connected in series Set output selection switches marked OUT1 through OUT4 to follow corresponding input IN1 IN2 and Connect FACP output to the desired AL800LGK9E logic board inputs and notification appliances to the desired AL800LGK9E logic board outputs see 02 Application Guide Note The 2 wire horn strobe sync mode will only synchronize horns horn strobes strobes with For connection of smoke detectors digital dialer see Hookup Diagram pg 7 output signal type Output Programming Selection Table pg 4 to the Fire Alarm System capability 3 A Style Z Class B Style W X Y SW1 SW2 Settings For all Class B Style W X Y hookups SW1 SW2 on the AL800LGK9E logic board must be open For all Class A Style Z hookups SW1 SW2 on the AL800LGK9E logic board must be closed Programming Selection Table must be programmed independently OUT1 OUT4 Positions to Output Follower Code 3 Mode Mode 3 2 follows signal it receives from the corresponding input FACP Sync module maintains synchronization of appliance circuit Temporal Code 3 signal generation output mode will accept a steady or a pulsing input 2 3 A steady output signal will be generated mode will accept steady or pulsing input the above modes Dip Switch 4 determines which Input controls corresponding output 4 in the ON position causes output s to be controll