Mircom MIX-2351TAPA Installation Manual - English

File Preview
File Preview
Click below to download for free

File Data

Name mircom-mix-2351tapa-installation-manual-english-9413862057.pdf
Type PDF
Size 894.29 KB
Downloads

Text Preview

I Technologies Ltd Interchange Way Vaughan ON L4K 5W3 905 660 4655 FAX 905 660 4113 AND MAINTENANCE INSTRUCTIONS Protocol Photoelectric and Sensors Voltage Range Current 24 VDC Alarm Current Current Humidity Range Temperature Range Velocity Load Rating refer to your isolator base module manual for isolator calculation instructions to 32 VDC uA one communication every 5 seconds with green LED blink on communication mA 24 VDC one communication every 5 seconds with red LED solid on mA 24 VDC one communication every 5 seconds with amber LED solid on to 93 Relative Humidity Non condensing to 115 0 to 47 to 4000 ft min 0 to 1219.2 m min 51 mm installed in B300A 6 Base 156 mm installed in B300A 6 Base 4.1 104 mm installed in B501A Base oz 95 g S529 listed for Open Air Protection S530 listed for Heat Detectors sensor must be installed in compliance with the control panel system manual The installation must meet the requirements of the Au Having Jurisdiction AHJ Sensors offer maximum performance when in compliance with CAN ULC S524 DESCRIPTION MIX 2351TAPA is a plug in type multi sensor smoke sensor that com a photoelectronic sensing chamber and 135 57.2 fixed tempera heat detector across addressable analog communications The sensors an analog representation of smoke density over a communication to a control panel Rotary dial switches are provided for setting the sen address See Figure 1 The intelligent photoelectric and temperature also transmit an alarm signal due to heat at 135 57.2 per CAN S530 1 ROTARY ADDRESS SWITCHES 0 0 GUIDE wiring must be installed in compliance with the Canadian Electrical Code local codes and any special requirements of the Authority Having Proper wire gauges should be used The installation wires should color coded to limit wiring mistakes and ease system troubleshooting Im connections will prevent a system from responding properly in the of a fire power from the communication line before installing sensors Wire the sensor base supplied separately per the wiring diagram Figure 2 Set the desired address on the sensor address switches see Figure 1 Install the sensor into the sensor base Push the sensor into the base while it clockwise to secure it in place After all sensors have been installed apply power to the control panel and the communication line Test the sensor s as described in the TESTING section of this manual covers provide limited protection against airborne dust particles during Dust covers must be removed before the sensors can sense smoke sensors prior to heavy remodeling or construction 2 WIRING DIAGRAM Do not loop wire under 1 or 2 Break wire run to connections A OPTIONAL WIRING and temperature sensors include a tamper resistant capability prevents removal from the base without the use of a tool Refer to the manual for details on making use of this capability C0129 11 LEDs on the sensor are controlled by the panel to indicate sensor status output is provided for connection to an optional remote LED annunciator RA100ZA panels offer different features sets across different models As a result features of the photoelectric and temperature sensors may be available some control panels but not on others MIX 2351TAPA supports Advanced and CLIP Classic Loop Interface Protocol mode The possible fea available if supported by the control panel are The sensor LEDs can operate in three ways off and blinking can be set to red green or amber This is controlled by the panel The remote output may be synchronized to the LED operation or con independent of the LEDs Devices are point addressable up to 159 addresses refer to the operation manual for the ULC listed control panel for spe operation The photoelectric and temperature sensors require compatible communications to function properly Connect these sensors to control panels only recommends spacing sensors in compliance with CAN ULC S524 In air flow applications with smooth ceilings space sensors 30 feet apart m When using the photoelectric and temperature sensors as a heat de in FM3210 compliant applications space sensors 20 feet apart 6 m specific information regarding sensor spacing placement and special ap refer to CAN ULC S524 or the System Smoke Detector Application available from Mircom testing notify the proper authorities that the system is undergoing and will temporarily be out of service Disable the system to unwanted alarms sensors must be tested after installation and periodically thereafter Test methods must satisfy the Authority Having Jurisdiction AHJ Sensors maximum performance when tested and maintained in compliance with S536 sensor can be tested in the following ways Functional Magnet Test P N M02 04 01 or M02 09 00 Hold the test magnet in the magnet test area as shown in Figure 3 This sensor can be functionally tested with a test magnet The test magnet simulates smoke in the sensing chamber testing the sensor and connections to the control panel The sensor should alarm the panel Two LEDs on the sensor are controlled by the panel to indicate sensor Coded signals transmitted from the panel can cause the LEDs to latch on or latch off Refer to the control panel technical documen for sensor LED status operation and expected delay to alarm Smoke Entry Sensitivity readings are available through the FACP Refer to the manufac published instructions for proper use Additionally canned aerosol simulated smoke canned smoke agent may used for smoke entry testing of the smoke detector Tested and ap aerosol smoke products are removing the detector notify the proper authorities that the smoke system is undergoing maintenance and will be temporarily out of Disable the zone or system undergoing maintenance to prevent un alarms Remove the sensor to be cleaned from the system Remove the sensor cover by pressing firmly on each of the four removal that hold the cover in place Vacuum the screen carefully without removing it If further cleaning is continue with Step 4 otherwise skip to Step 7 Remove the chamber cover screen assembly by pulling it straight out Use a vacuum cleaner or compressed air to remove dust and debris from sensing chamber Reinstall the chamber cover screen assembly by sliding the edge over the chamber Turn until it is firmly in place Replace the cover using the LEDs to align the cover and then gently push it until it locks into place Make sure that the thermistors do not be bent under the cover Reinstall the detector Test the detector as described in TESTING Reconnect disabled circuits Notify the proper authorities that the system is back on line NOTE REGARDING SMOKE DETECTOR GUARDS detectors are not to be used with detector guards unless the combina has been evaluated and found suitable for that purpose 3 FEATURES OF THE PHOTO HEAT DETECTOR Alignment Notch Fire Safety Climb 30S PURCHECK CENTURIAN SOLOA4 TRUTEST 2000 used properly the canned smoke agent will cause the smoke detector go into alarm Refer to the manufacturer published instructions for proper of the canned smoke agent aerosol simulated smoke canned smoke agent formulas will vary by Misuse or overuse of these products may have long term ad effects on the smoke detector Consult the canned smoke agent manufac published instructions for any further warnings or caution statements Direct Heat Method Hair dryer of 1000 1500 wat

Related Files