Notifier NFS-3030 Frame & Post
File Preview
Click below to download for free
Click below to download for free
File Data
Name | notifier-nfs-3030-frame-post-7540831962.pdf |
---|---|
Type | |
Size | 1019.31 KB |
Downloads |
Text Preview
NFS 3030 E OPERATING INSTRUCTIONS 1 Operating Information Standby Operation Green POWER indicator lit steadily Red FIRE ALARM indicator off Yellow TROUBLE indicators off Condition Red FIRE ALARM indicator lit Alarm signaling devices activated Option module remote station or supplementary alarm relay activated Alarm information visible on LCD liquid crystal display Reset After locating and correcting the alarm condition reset the panel by pressing the SYSTEM RESET switch Condition Activation of trouble signal under normal operation a condition that requires immediate attention Contact your local service Silence the audible signal by pressing the ACKNOWLEDGE switch trouble indicator will remain illuminated 2 CPU 3030 Switch Functions This silences the piezo sounder and changes all flashing to steady It sends an acknowledge message to the printer and history ACKNOWLEDGE also automatically sends a special command to silence piezo on ACS Annunciators If more than one event exists it advances the to the next item and displays it until the ACKNOWLEDGE switch is pressed Only one press is necessary for non fire trouble or supervisory signals SILENCE SIGNAL SILENCE turns off all silenceable circuits and the SIGNALS SILENCED indicator It also sends a SIGNALS SILENCED to the LCD printer and history file A subsequent alarm will then the system This unit is programmed to inhibit signal silence for seconds This unit is programmed to automatically silence alarm signal after The NFS 3030 waits for the DRILL switch to be pressed for 2 seconds to accidental activations then turns on all silenceable circuits all control circuits that are programmed silenceable and turns off the SILENCED LED This event shows on the LCD printer and History file This switch is only available on NFS 3030 with keypad display RESET Resets the control panel in standalone applications Resets when enabled in network applications TEST Press and hold the switch to lamp test the LEDs 3 LED Indicators Green LED which illuminates when primary power is applied to the panel Alarm Red LED that flashes when one or more alarms occur Illuminates after alarms are acknowledged and turns off when SYSTEM RESET is after alarm clears Red LED that flashes when a pre alarm threshold is reached Blue LED that illuminates for a security alarm LED turns off after alarm clears and SYSTEM RESET is pressed Yellow LED that flashes when a Supervisory or Tamper occurs such as a sprinkler valve tamper condition The LED illuminates after conditions are acknowledged and turns off when the conditions are The Tamper indication will latch until SYSTEM RESET is pushed Trouble Yellow LED that flashes when one or more troubles occur on steadily when ACKNOWLEDGE is pressed and turns off when all trouble are cleared Event Future use Silenced Yellow LED that illuminates after SIGNALS SILENCED has pressed Turns off when DRILL or SYSTEM RESET is pressed Disabled Yellow LED that illuminates when one or more points are The LCD will indicate which points have been disabled Turns off when are re enabled Failure Yellow LED that illuminates if the microprocessor fails 4 CPU 3030 Audible Sounder A continuous sounding tone Two beeps per second Four beeps per second Eight beeps per second 5 Periodic Testing and Maintenance ensure proper and reliable operation system inspection and testing should be monthly or as required by NFPA 72H or local fire codes A qualified Representative should perform testing Testing Notify fire department and or central alarm receiving station alarm condition is transmitted Notify facility personnel of the test so alarm devices are ignored during the test period Connection Feature ULC requires that devices such as and TM 4 be disconnected during annual testing to prevent transmission false alarms Disable by turning the internal AKS 1 keyswitch Slide SW4 Disable All Output switch from to Testing Verify that remote connection devices are turned back on all fire central station and or building personnel when testing is complete 6 Audio Telephone System Information 6 applies to voice and telephone systems only Audio Message Generator Level This green LED is illuminated when the audio level is correct Call This green LED toggles ON and OFF with each press of the All Call Line This green LED normally illuminates to show that the control panel is with the Audio Message Generator This yellow LED illuminates to indicate the presence of a trouble local the audio equipment AMG 1 FFT 7 FFT 7S and amplifiers Call switch The All Call switch when pressed is used to activate all circuits These speaker circuits will deactivate when the All Call switch is again toggle function provided an alarm is not present If an alarm is the speaker circuits will return to the state held previous to the All Call In applications press either All Call switch for the same result Volume The local speaker volume control adjusts the volume of the located on the AMG 1 It will not affect the volume of the speakers throughout the facility If necessary turn the volume down to prevent during paging operations The microphone is used for paging operations To page select the circuit s that you wish to page to by using the control switches on the DCM 4RK or ACS annunciators or by using the All Call switch on AMG 1 Press the switch on the side of the microphone and speak into the Talk loudly enough to cause the green Audio Level LED to If the Audio Level LED remains off for 30 seconds a system trouble result Circuit Select To turn a speaker circuit on press the control button a specific speaker circuit on the VCM 4RK DCM 4RK or ACS annunciators LED for the circuit selected will illuminate The control button toggles the of this circuit Select To select an audio output function voice message or tone press the control button Note An active audio function may have to deactivated before selecting the next function Select To select a channel press the control button on the for the desired channel The LED on that point will illuminate The button toggles the selection of the channel Channels must be selected for speaker zone in a dual channel system and FFT 7S Fire Fighters Telephone Mode FFT 7 only The green LED will illuminate when the Page switch depressed Line This green LED will illuminate to show that power is applied to the Trouble This yellow LED illuminates to indicate an internal circuit Trouble This yellow LED illuminates to indicate an external circuit Switch The Page switch allows the firefighter to page from the FFT 7 To select the speaker circuits that will carry the page by using the control button by using the All Call switch on the adjacent AMG 1 Press the Page switch and loud enough into the handset to cause the green audio level LED on the to illuminate Calls The green LED on the VCM 4RK mapped to a telephone will flash and the piezo will beep DO NOT PRESS THE ACKNOWLEDGE IN THIS CASE To answer the incoming call pick up the master and press the control button Wait until the caller is connected audible in the receiver To disconnect the call momentarily press the telephone control button again Paging Answer the incoming call as described above Press the Page on the FFT 7 and select the required speaker circuits by using the control or the All Call switch on the adjacent AMG 1 Any caller connected to the from a remote location can now page to the selected speaker circuits 7 Local Service Representative NUMBER Manuals Online sheet must be framed and mounted adjacent to the control panel 51851 Rev B ECN 02 266 4 25 2002