System Sensor PDRP-1001-PDRP-1001A-PDRP-1001E Deluge-Preaction Control Panel
File Preview
Click below to download for free
Click below to download for free
File Data
Name | system-sensor-pdrp-1001-pdrp-1001a-pdrp-1001e-deluge-preaction-control-panel-6718329405.pdf |
---|---|
Type | |
Size | 1.89 MB |
Downloads |
Text Preview
System Sensor Ohio Avenue Charles IL 60174 630 377 6495 PDRP 1001 PDRP 1001A PDRP 1001E Preaction Control Panel 50734 50734 C C 99 166 Precautions Adherence to the following will aid in problem free installation with long term reliability Several different sources of power can be connected to the alarm control panel Disconnect all sources of power before Control unit and associated equipment may be damaged by and or inserting cards modules or interconnecting cables the unit is energized Do not attempt to install service or operate unit until this manual is read and understood System Reacceptance Test after Software Changes To proper system operation this product must be tested in with NFPA 72 1993 Chapter 7 after any programming or change in site specific software Reacceptance testing is after any change addition or deletion of system components or any modification repair or adjustment to system hardware or components circuits system operations or software functions known be affected by a change must be 100 tested In addition to ensure other operations are not inadvertently affected at least 10 of devices that are not directly affected by the change up to a of 50 devices must also be tested and proper system verified system meets NFPA requirements for operation at 0 49O C F and at a relative humidity of 85 RH non condensing at C 86O F However the useful life of the system standby batteries the electronic components may be adversely affected by extreme ranges and humidity Therefore it is recommended that this and its peripherals be installed in an environment with a nominal temperature of 15 27O C 60 80O F that wire sizes are adequate for all initiating device loops Most cannot tolerate more than a 10 I R drop from the specified voltage Alarm System Limitations automatic fire alarm system typically made up of smoke heat detectors manual pull stations audible warning devices a fire alarm control with remote notification capability can provide warning of a developing fire Such a system however does not protection against property damage or loss of life resulting from a fire alarm system may fail for a variety of reasons detectors may not sense fire where smoke cannot reach the such as in chimneys in walls or roofs or on the other side of doors Smoke detectors also may not sense a fire on another or floor of a building A second floor detector for example may not a first floor or basement fire Furthermore all types of smoke both ionization and photoelectric types have sensing No type of smoke detector can sense every kind of fire by carelessness and safety hazards like smoking in bed violent escaping gas improper storage of flammable materials electrical circuits children playing with matches or arson Smoke detectors must be installed in the same room as control panel and in rooms used by the system for the connection of transmission wiring communications signaling and or power If are not so located a developing fire may damage the alarm crippling its ability to report a fire Warning all solid state electronic devices this system may operate or can be damaged when subjected to lightning induced Although no system is completely immune from lightning and interferences proper grounding will reduce Overhead or outside aerial wiring is not recommended to an increased susceptibility to nearby lightning strikes Consult the Technical Services Department if any problems are or encountered AC power and batteries prior to removing or inserting boards Failure to do so can damage circuits all electronic assemblies prior to any drilling filing reaming punching of the enclosure When possible make all cable entries the sides or rear Before making modifications verify that they not interfere with battery transformer and printed circuit board not tighten screw terminals more than 9 in lbs Over tightening damage threads resulting in reduced terminal contact pressure difficulty with screw terminal removal system contains static sensitive components Always ground with a proper wrist strap before handling any circuits so that charges are removed from the body Use static suppressive to protect electronic assemblies removed from the unit the instructions in the installation operating and manuals These instructions must be followed to avoid to the control panel and associated equipment FACP and reliability depend upon proper installation installing a fire alarm system may make lower insurance possible it is not a substitute for fire insurance warning devices such as bells may not alert people if these are located on the other side of closed or partly open doors or located on another floor of a building fire alarm system will not operate without any electrical power If power fails the system will operate from standby batteries only for specified time heat detectors may be subject to reduced sensitivity time For this reason the rate of rise feature of each detector be tested at least once per year by a qualified fire protection used in the system may not be technically compatible the control panel It is essential to use only equipment listed for with your control panel lines needed to transmit alarm signals from a premise to a monitoring station may be out of service or temporarily most common cause of fire alarm malfunctions however is maintenance All devices and system wiring should be and maintained by professional fire alarm installers following procedures supplied with each device System inspection and should be scheduled monthly or as required by National and or fire codes Adequate written records of all inspections should be This equipment generates uses and can radiate radio energy and if not installed and used in accordance with the manual may cause interference to radio communications It been tested and found to comply with the limits for class A device pursuant to Subpart B of 15 of FCC Rules which is to provide reasonable protection against such interference operated in a commercial environment Operation of this in a residential area is likely to cause interference in which the user will be required to correct the interference at his own Requirements digital apparatus does not exceed the Class A limits for radiation emissions from digital apparatus set out in the Radio Regulations of the Canadian Department of present appareil numerique n pas de bruits radioelectriques les limites applicables aux appareils numeriques de la A prescrites dans le Reglement sur le brouillage edicte par le ministere des Communications du PDRP 1001 PN 50734 C 03 11 99 The PDRP 1001 PDRP 1001A PDRP 1001E of Contents Standards 5 Information 5 6 6 Circuits 6 circuits optional auxiliary relays track these four circuits 6 Panel Control Switches 7 Boards 8 Module 4XTM NOTIFIER 8 Interface Module 4XLM NOTIFIER 8 Relay Module 4XZM NOTIFIER 8 Module 4XTM NOTIFIER 8 Remote Station service NFPA 72 Remote Station Fire Alarm System 9 Interface Module 4XLM NOTIFIER 9 Relay Module 4XZM NOTIFIER 9 Annunciator