Potter 550-0622-AAE Potter PAD200 6DB 4DB Series

File Preview
File Preview
Click below to download for free

File Data

Name potter-550-0622-aae-potter-pad200-6db-4db-series-6748391520.pdf
Type PDF
Size 1.66 MB
Downloads

Text Preview

550 0622 000 Bases PAD100 4DB PAD100 PHD PAD200 PD PAD200 PHD PAD200 PCHD PAD100 HD and PAD100 CD Description document provides instructions for mounting and wiring the Detector PAD100 6DB and PAD100 4DB The following detectors are compatible Detector Base PAD100 6DB and PAD100 4DB PAD200 PD PAD100 PD PAD200 PHD PAD100 PHD Photoelectric Smoke Heat Detector Smoke CO Detector PAD200 PCD Smoke CO Detector Heat Detector PAD200 PCHD Detector PAD100 HD PAD100 CD Monoxide Detector Smoke Detector Field Wiring Diagrams field wiring diagrams for the Signaling Line Circuit SLC FIGURE 1 SLC supports NFPA wiring Class B A and X THE DETECTORS AND THE PAD100 MODULES MUST HAVE ADDRESS ES To install the detector head onto the base match the detector heads the base using the alignment feature and twist clockwise until the heads snap into place FIGURE 2 Features FACP SLC Detector Base Detector Base 1 Wiring Style B PAD100 6DB or PAD100 4DB of NFPA Style B SLC S S Wiring using either the PAD100 6DB or base FIGURE 1 In Style A arrangement two separate would return from the last detector base to a listed compatible Alarm Control Panel FACP In Style X it is required to use PAD100 IB Isolator Bases and typical field diagram is in the PAD100 IB Manual be dressed properly at the time of installation NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 72 OF ARTICLE 300.3 B OF THE NATIONAL ELECTRICAL NFPA 70 AS WELL AS ARTICLE 210 Wiring Instruction To ensure proper installation of the detector head to the base wires Using PAD100 Bases observe the correct polarity of SLC wiring WIRING TO BE USED SHALL BE IN ACCORDANCE WITH THE THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH Break wire runs to provide supervision for connections made to wire pair Base Mounting PAD100 4DB should be mounted directly on the electrical box PAD100 6DB mounting holes are configured for a single gang double octagon or 4 square box The PAD100 4DB mounting holes are for a 3 1 2 octagon box Use a box for each base and run the circuit to all base locations 12 to 22 AWG conductors to connect to terminals of bases It is that the SLC conductors be color coded to avoid wiring errors assist in system troubleshooting Improper SLC connections may the system from operating normally Disconnect power to the SLC the detectors are installed Wire the detector bases according to Field Wiring Diagrams Use the dip switches SECTION 11 to set address es 1 127 for each head 2 Assembly of Detector apply power to the FACP After all detector heads addressable bases and modules have been Test the detectors as described in the Testing Section of this manual DO NOT INSTALL DETECTOR HEADS UNTIL AREA HAS BEEN CLEANED TO REMOVE CONSTRUCTION DEBRIS DUST AS REQUIRED BY NFPA 72 Spacing Limitations REFER TO NFPA 72 FOR SPECIFIC INFORMATION REGARDING SPACING MOUNTING LOCATION AND SPECIAL APPLICATIONS PAD200 PD PAD200 PCD PAD200 PCHD PAD100 PHD and Photoelectric Smoke Detector PAD200 PD PAD200 PCD PAD200 PCHD PAD100 PHD and PAD200 are ANSI UL listed on maximum 30ft spacing limitation with alarm set point 135O 174O F on smooth ceiling Refer to NFPA 72 for specific information detector spacing placement and special applications Heat Detector ANSI UL listed spacing limitations of PAD100 HD smooth ceiling are Set Point to 174O F to 79O C to 185O F to 85O C to 160O F to 71O C of Rise Spacing Temperature Spacing 60 ft 60 ft 15 ft 15 ft 70 ft 70 ft on alarm set point Testing shall be performed periodically to determine if each detector properly Detectors will offer maximum performance when tested compliance with NFPA 72 REFER TO FIRE ALARM CONTROL PANEL FACP MANUAL FOR OF DIRTY VALUE READ PRINT ALARM AND WALK TEST Number 550 0622 3 Removing Detector Cover PD models only the two screws on back of detector remove detector cover DO NOT USE A DRIVER WHEN SCREWS shown DO NOT THE OPTIC OR METAL SCREEN THAT IS THE OPTIC AVOID CIRCUIT WHEN IS USE CLEAN AIR shown up pin holes on cage base to pins circuit board base shown Testing PAD100 PD PAD200 PD PAD100 PHD PAD200 PHD PAD200 PCD PAD100 HD and PAD100 CD are under normal conditions in mode the alarm indicator LEDs on the face of the detector will pulse once every 4 seconds WHEN A PANEL IS CONFIGURED TO NOT FLASH LEDS THE LEDS THE DETECTORS WILL NOT FLASH AT ANY TIME Testing Value Read Print sensitivity drift value Dirty Value of the smoke detector can be checked the FACP The Dirty Value can be read and printed out at the FACP DETECTOR COMPENSATES SENSITIVITY UNTIL LIMIT OF WHEN COMPENSATION RATE REACHES LIMIT A SIGNAL WILL BE INDICATED ON THE FACP Testing BE SURE TO DIS ENGAGE ALL ALARM SIGNAL SERVICES DEVICES AND EXTINGUISHING SYSTEMS PRIOR TO THE FOLLOWING TEST EXCEPT AUTOMATIC TESTING BY FACP BE SURE TO RE ENGAGE THESE SYSTEMS WHEN ALL TESTING COMPLETE Test FACP must be placed into Walk Test Mode and follow the steps below the appropriate steps outlined below for the detector that is to be FAILURE TO ALARM DURING A TEST INDICATES A DETECTOR REPLACE DETECTOR IMMEDIATELY PAD100 PD PAD200 PD PAD200 PCD PAD200 PCHD PAD100 PHD and Smoke Detectors Use a ANSI UL listed aerosol such as Safeguard Model 25S or SDi Smoke Centurion as acceptable to the Having Jurisdiction AHJ Do not heat over 210oF 98.9oC nozzle PAD100 PHD PAD200 PCHD PAD200 PHD and PAD100 HD Heat TAKE CARE DURING THE HEATING OF THE DETECTOR TO AVOID THE PLASTIC HOUSING of a low powered heat gun is acceptable Maintain a minimum of 1 foot between the detector and the heat Heat the detector for a minimum of 10 seconds FACP will indicate with alarm when a sufficient amount of heat has applied LED indicator will continuously flash while detector is alarm PAD100 CD PAD200 PCD PAD200 PCHD Carbon Monoxide Detectors the Home Safeguard Model HO CO2 Aerosol with Home Safeguard Versa Test Head VT1 or the SDI Solo C6 Aerosol with SDI Solo 330 as acceptable to the Authority Having Jurisdiction AHJ IN WATER WATER CAN AFFECT THE SENSOR CAUSING DAMAGE NEVER USE EXHAUST FROM VEHICLE TO TEST CO PORTION OF EXHAUST MAY CAUSE PERMANENT DAMAGE TO DETECTOR VOIDS THE WARRANTY Maintenance detector should be cleaned as needed Detectors installed in more prone to dust may need cleaning based on build up dust The Dirty Value Report provides an indication when the detectors be cleaned THE DETECTOR IS NOT WASHABLE DO NOT SUBMERGE THE DO NOT SPRAY CLEANING CHEMICALS OR INSECT SPRAYS DIRECTLY ON OR NEAR THE DETECTOR DO NOT PAINT OVER THE DETECTOR SO MAY CAUSE PERMANENT DAMAGE PAD100 PHD PAD200 PHD PAD200 PCD PAD200 PCHD PAD100 HD and When cleaning is needed clean cover using a soft cloth NOT vacuum or use compressed air water cleaners or solvents NOT disassemble the detector to clean PAD100 PD and PAD200 PD When cleaning is needed follow the below to remove dust on the detector Turn off electrical power to the PAD100 PD and PAD200 PD Remove the detector from the base Do not remove the base from Remove cover from detector by removing the two screws T10 on DO NOT USE A POWER DRIVER WHEN REMOVING INSTALLING the detector is not operating properly after cleaning replace of detector FIGURE 3 clean the detector wall up pins on board base to holes on optic base 4 Remove Optic Cage Base from Detector for Cleaning PD models only 5 Pin Holes on Back of Optic Cage Base PD models only Remove optic cage base from the circuit

Related Files