Potter Installation Manual PAD100-MIM Micro Input Module

File Preview
File Preview
Click below to download for free

File Data

Name potter-installation-manual-pad100-mim-micro-input-module-0452813697.pdf
Type PDF
Size 850.10 KB
Downloads

Text Preview

Installation Manual PAD100 MIM Micro Input Module TO THE INSTALLER manual provides an overview and the installation instructions for the PAD100 MIM module This module is only compatible addressable fire systems that utilize the PAD Addressable Protocol terminals are power limited and should be wired in accordance with the requirements of NFPA 70 NEC and NFPA 72 National Alarm Code Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended For information refer to the control panel installation instructions module shall only be installed with listed control panels Refer to the control panel installation manual for proper system Description PAD100 MIM is used to monitor the status of an initiating device s that contain a normally open set of dry contacts The is enclosed in a plastic case to protect against inadvertent shorts and ground faults The case can be mounted using a screw Generally the PAD100 MIM is used to monitor pull stations and other devices where the module is installed in an box or enclosure behind the device being monitored PAD100 MIM includes one red LED to indicate the module status In normal condition the LED flashes when the device is polled by the control panel When an input is activated the LED will flash at a fast rate If the LED blink has been disabled the programming software in a normal condition the LED of the device will be off All other conditions remain the same Setting the Address PAD protocol detectors and modules require an address prior to connection to the panel SLC loop Each PAD device i e detector and or module is set by changing the dip switches located on the device PAD device addresses are of a seven 7 position dip switch used to program each device with an address ranging from 1 1 PAD Device Dip Switch Addresses Table Addresses 1 16 32 64 16 32 64 16 32 64 16 32 64 16 32 64 16 32 64 16 32 64 Each gray box indicates that the dip switch is On and each white box indicates Off 16 32 64 16 32 64 16 32 64 examples shown below illustrate a PAD device dip switch settings the 1st example shows a device not addressed where all switch settings are in the default Off position the 2nd illustrates an addressed PAD device via the dip switch settings 2 Examples of PAD Device Showing Default Dip Switch Setting Unaddressed Addressed PAD Device 4 64 4 64 dip switches are in the Off shows this PAD device 42 Dip switches 2 8 are in the On position Electric Signal Company LLC St Louis MO Phone 800 325 3936 www pottersignal com 5406302 A 02 16 PAGE 1 OF 2 connecting a device to the SLC loop take the following precautions to prevent potential damage to the SLC or device Technical Specifications to the SLC is removed wiring on module is correctly installed wiring has no open or short circuits Voltage SLC Standby Current SLC Alarm Current Input Circuit Wiring Resistance of IDC Wiring Capacitance of IDC IDC Voltage IDC Current Resistor Temperature Range Humidity Range no of Module Per Loop Options Weight A A B VDC A to 120 F 0 to 49 C to 93 non condensing units L x 1.36 W x 43 D deep single gang box lbs Wiring Diagram is an wiring diagram showing how to wire a PAD100 MIM module to the panel 3 Example of Wiring a PAD100 MIM wiring style supports the Class A Class B and Class X wiring style is Class B loop wiring SLC SLC and initiating device wiring IN power limited Wiring for terminals SLC SLC are supervised Wiring for terminals IN are supervised Wire Preparation Strip all wires 1 4 inch from their edges as addressable module does not support 2 wire detectors wiring is between 12 max and 22 min here inch Stripping too much insulation may cause a ground fault Stripping too little may cause a poor connection and an open circuit FACP OR PREVIOUS AND TO NEXT DEVICE NORMALLY OPEN DEVICE OHM REQUIRED 3005013 instructions do not purport to cover all the details or variations in the equipment described nor provide for every contingency to be met in connection with installation operation and maintenance subject to change without prior notification Technical Assistance contact Potter Electric Signal Company at 866 956 1211 performance is based on proper application of the product by a qualified professional further information be desired or should particular problems arise which are not covered sufficiently for the purpose the matter should be referred to a distributor in your region PAGE 2 OF 2 MANUAL PAD100 MIM MICRO INPUT MODULEDocument 5406302 A 02 16Potter Electric Signal Company LLC St Louis MO Phone 800 325 3936 www pottersignal comfirealarmresources com

Related Files