FM 200TM Extinguishing Systems Trip ENGINEER AND ARCHITECT SPECIFICATIONS Mechanical Closing of or Doors Operated Only by Pressure of Discharge Connected Anywhere in Discharge Foot Length of Connecting or Tubing Listed Approved Pressure Trip is activated by the FM 200TM pressure in system piping at the time of system discharge It is to release door or damper closing hardware or other or spring operated devices Trip damper release is recommended for vent which continue to move air during a deceleration following electrical fan shut down The use of a delay timer to allow for the deceleration period have no effect if the system is discharged mechanically dampering is necessary for sound design Pressure Trip is designed for a maximum load of 100 This is based on a minimum pressure of 75 at the Pressure Trip pressure is obtained from the outlet of a tree anywhere in the discharge piping Connection from tree to the pressure switch can be made with inch 40 pipe and 300 pound class malleable iron or iron fittings The maximum length of connecting or pipe is 100 feet Specifications Pressure Trip shall be provided to release damper or closing hardware upon actual discharge of FM 200TM the system piping so as to assure damper or door in the event of mechanical release of the system Information No Trip Weight NUMBER Pyrotronics Ridgedale Avenue Knolls NJ 07927 201 267 1300 201 397 7008 in U S A Pyrotronics East Pearce Street Hill Ontario 1B7 CN 905 764 8384 905 731 9182 1996 sheet dated 9