Siemens CPY-PLT Nitogen Pilot Cylinder, Data sheet

File Preview
File Preview
Click below to download for free

File Data

Name siemens-cpy-plt-nitogen-pilot-cylinder-data-sheet-2756098431.pdf
Type PDF
Size 1.16 MB
Downloads

Text Preview

Sheet Safety Products Engineered Fire Suppression Systems Cylinder CPY PLT AND ENGINEER SPECIFICATIONS Cylinder valve assembly is the same size as a 15.87 kg cylinder tank assembly Total distance of 600 feet 182.88 meters of clean agent in one 1 direction Distance up to 300 feet 91.44 meters two 2 directions Discharge port is fitted with either a factory supplied anti plug or with Sinorix nozzle Model CPYEN2 1 0.0551 UL 2166 Listed Standard for Halocarbon Clean Agent Extinguishing System Units Overview Pilot Cylinder Model CPY PLT from Siemens Inc Fire Safety is used as part of the Sinorix Fire Suppression System CPY PLT is the equivalent size of a Sinorix 35 15.9 kg cylinder assembly and features a cylinder acting as the pilot cylinder use of a Model CPY PLT cylinder allows pneumatic 50 feet 15.24 meters from the main cylinder Total coverage distance of 600 feet 182.88 meters suppression clean agent in one 1 direction Coverage distance up to 300 feet 91.44 meters two 2 directions to Figures A and B in the Diagram section Page 2 for more detail on the extended allowed with use of a Model CPY PLT Industry Inc Technologies Division CYLINDER discharge port of each Model CPY PLT can either fitted with the factory supplied anti recoil plug it can be fitted with Sinorix nozzle CPYEN2 1 Additionally the discharge port can be into the protected hazard area parts used for the entire Sinorix Engineered Suppression System is UL 2166 Listed for Ordering and Part Number Pilot Cylinder Cylinder Sinorix 6638 no time can the total length of copper tubing and the flex hose exceed 300 feet 91.44 m in two 2 directions or 600 feet 182.88 m in one 1 direction Diagrams A Pilot Cylinder with one 1 Main Cylinder Pilot Cylinder with one 1 Primary Cylinder and one 1 Secondary Cylinder B This marketing data sheet is not intended to be used for system design or installation purposes the most up to date information refer to each product installation instructions Industry Inc Technologies Division Safety Fernwood Road Park NJ 07932 973 593 2600 908 547 6877 www usa Siemens com Fire in U S A Safety North Service Road Oakville Ontario 0H6 Canada 905 465 8000 www Siemens CA 2016 sheet dated 10 2016 1

Related Files