Siemens PAD-3-UK Upgrade Kit, Installation Instructions

File Preview
File Preview
Click below to download for free

File Data

Name siemens-pad-3-uk-upgrade-kit-installation-instructions-8950734612.pdf
Type PDF
Size 609.75 KB
Downloads

Text Preview

Installation Instructions PAD 3 UK Upgrade Kit Safety the SIEMENS Model PAD 3 UK kit to upgrade PAD 3 to the latest released firmware GUIDELINES follow the installation instructions below to the PAD 3 firmware CAUTION equipment is extremely vulnerable to discharge Extreme care should be taken performing this upgrade Notify the person in charge of the fire alarm and the Fire Department if they are to the system that the control panel be temporarily out of service while the upgrade is installed Power down the system battery first then AC Remove U11 PAD 3 firmware Do this by lifting end of the IC slightly then the other end this process until the IC comes free a short thin blade screwdriver for best Remove the new PAD 3 IC from its packaging and check to see that all of the pins straight Straighten any that are not Place the new PAD 3 IC in the socket for U11 the notch in the end of the IC to the left indicated by the silkscreen outline on the PC Be sure that all of the pins go into the socket holes Press down firmly to seat IC properly Power up the system AC first then battery If you are upgrading from Firmware Revi 1 xxx the AC Power Fault Reporting Delay set by the 10 position DIP switch will change follows Building Technologies Inc Fernwood Road Park New Jersey 07932 315 648449 2 Building Technologies Ltd Derry Road West Ontario L5N 7A6