Siemens RR-3S Remote Detector Relay, Installation Instructions

File Preview
File Preview
Click below to download for free

Text Preview

Installation Instructions RR 3S Detector Relay 1 the RR 3S Relay Assembly 2 the RR 3S Mount the RR 3S Relay assembly to the of the base as shown in Figure 1 the screws supplied Use a 4 inch square deep outlet box for detector base Route all wires outward the outlet box Terminate the relay contact wiring as on the connection diagram in 2 Route the black and yellow wires from the assembly and detector wiring the cross cuts in the center of the Mount the base to the outlet box and make connections directly to the base Terminate the yellow wire from RR 3S at terminal 1b on the base and black wire from RR 3S at terminal 6 on base all remaining wiring according to the for the base P N 315 083225 Do not use a remote lamp with base when RR 3S is used RATINGS 125 VAC 30 VDC Resistive Industry Inc Technologies Division Park NJ 315 094955 4 Building Technologies Ltd Safety Security Products Kenview Boulevard Ontario 5E4 Canada