Silent Knight 5600 Installation Manual

File Preview
File Preview
Click below to download for free

File Data

Name silent-knight-5600-installation-manual-6214807593.pdf
Type PDF
Size 1.91 MB
Downloads

Text Preview

INTELLIKNIGHT 5600 5600C Fire Control Panel and Manual 151450 Rev E2 ECN 13 0232 ECN 13 0232 Procedure Precautions Adherence to the following will aid in problem free with long term reliability WARNING Several different sources of power be connected to the fire alarm control panel Disconnect all sources of power servicing Control unit and associated equipment may be damaged by and or inserting cards modules or interconnecting cables while the unit is Do not attempt to install service or operate this unit until manuals are and understood CAUTION System Re acceptance Test after Software To ensure proper system operation this product must be tested in with NFPA 72 after any programming operation or change in site specific Re acceptance testing is required after any change addition or deletion of components or after any modification repair or adjustment to system or wiring All components circuits system operations or software functions to be affected by a change must be 100 tested In addition to ensure that operations are not inadvertently affected at least 10 of initiating devices that not directly affected by the change up to a maximum of 50 devices must also be and proper system operation verified This system meets NFPA requirements operation within the range of 0 32 or humidity within the range 10 93 at 30 86 noncondensing However the useful life of the system batteries and the electronic components may be adversely affected by temperature ranges and humidity Therefore it is recommended that this and its peripherals be installed in an environment with a normal room of 15 27 C 60 80 F Verify that wire sizes are adequate for all and indicating device loops Most devices cannot tolerate more than a 10 drop from the specified device voltage Like all solid state electronic devices system may operate erratically or can be damaged when subjected to lightning transients Although no system is completely immune from lightning and interference proper grounding will reduce susceptibility Overhead or aerial wiring is not recommended due to an increased susceptibility to lightning strikes Consult with the Technical Services Department if any are anticipated or encountered Remove DC power prior to removing or circuit boards Failure to do so can damage circuits Remove all electronic prior to any drilling filing reaming or punching of the enclosure When make all cable entries from the sides or rear Before making modifications that they will not interfere with battery transformer or printed circuit board Do not tighten screw terminals more than 9 in lbs Over tightening may threads resulting in reduced terminal contact pressure and difficulty with terminal removal Fire alarm control panels contain static sensitive Always ground yourself with a proper wrist strap before handling any so that static charges are removed from the body Use static suppressive to protect electronic assemblies removed from the unit the instructions in the installation operating and programming manuals instructions must be followed to avoid damage to the control panel and equipment FACP Fire Alarm Control Panel operation and reliability upon proper installation used in the system may not be technically compatible with the control It essential to use only equipment listed for service with your control panel lines needed to transmit alarm signals from a premise to a central station may be out of service or temporarily disabled The most common of fire alarm malfunctions however is inadequate maintenance All devices system wiring should be tested and maintained by professional fire alarm following written procedures supplied with each device System inspection testing should be scheduled monthly or as required by national and or local fire Adequate written records of all inspections should be kept 1 1 Overview of Basic System 1 Hardware Features 1 Software Features 1 About this Manual 2 Terms Used in this Manual 2 Compatible Products 2 How to Contact Silent Knight 2 2 Listings Approvals and Requirements 1 Communications Commission FCC 1 Underwriters Laboratories UL 3 Requirements for All Installations 3 Requirements for Central Station Fire Alarm Systems 4 Requirements for Local Protected Fire Alarm Systems 4 Requirements for Remote Station Protected Fire Alarm Systems 4 ULC Requirements 4 3 You Begin Installing 1 What in the Box 1 Environmental Specifications 1 Electrical Specifications 2 Wiring Specifications 3 Board Assembly Diagram 5 Calculating Current Draw and Standby Battery 6 Worksheet Requirements 6 Current Draw Worksheet for 5600 for UL 864 7 Current Draw Worksheet for 5600 ULC 9 Maximum Battery Standby Load for UL 864 11 Maximum Battery Standby Load for ULC 11 4 Panel Installation 1 Mounting the Control Panel Cabinet 1 Preventing Water Damage 1 Removing the 5600 Assembly from the Housing 1 Dead Front Installation and removal 2 Installation Manual Installing the Dead Front 2 Dead Front Removal 3 AC Power Connection 4 AC Power Connection for UL 864 applications 4 AC Power Connection for Canadian Applications 5 Battery Connection

Related Files