Text Preview
Remote Voice Module Instructions EVS RVM Remote Voice Module is within the EVS RCU Remote Unit It provides a supervised for live communication and an for the Emergency Voice System Installation and wiring of this device must be done in with NFPA 72 and local ordinances EVS RVM is compatible with the 5820XL EVS For programming DIP switch settings refer to Installation for 5820XL EVS PN LS10061 Layout Mounting Open the cabinet door and the dead panel Remove AC power and disconnect the batteries from the main control Mount the EVS RVM in the middle of the dead front on the six studs See Figure 1 Address Front Panel Holes 1 Back View of EVS RVM Current 60 mA Current 80 mA to a FACP Figure 2 to properly wire the EVS RVM the FACP SBUS Supervised Power Limited 2 Wiring the EVS RVM to the FACP PN LS10065 001SK E Rev A 13 0146 Remote Voice Module Installation Instructions the Microphone Figure 5 install the microphone Clip the microphone into the microphone See Figure 3 3 Sliding Microphone into Microphone Clip microphone cord through hole at bottom of the dead front panel See 4 5 Installing Strain Relief Clip Push the strain into the hole in the dead panel Restore AC power and reconnect the batteries 4 Microphone Cord Inserted Through Dead Panel Hole Attach strain relief clip to microphone The strain relief clip should have 2 of microphone cord through it Document LS10065 001SK E Rev A