Silent Knight IDPion isheet
File Preview
Click below to download for free
Click below to download for free
File Data
Name | silent-knight-idpion-isheet-0186294357.pdf |
---|---|
Type | |
Size | 698.36 KB |
Downloads |
Text Preview
GENERAL DESCRIPTION IDP Ion is an intelligent sensor that uses a state of the sensing chamber This sensor is designed to provide open protection and is intended for use with compatible control only Two LEDs on each sensor light to provide a local sensor indication Remote LED annunciator capability is as an optional accessory Part No RA400Z refer to the operation manual for the UL listed control for specific operation of the IDP Ion IDP Ion requires compatible addressable to function properly Connect this sensor to control panels only Knight recommends spacing sensors in compliance with 72 In low air flow applications with smooth ceilings sensors 30 feet apart For specific information regarding spacing placement and special applications refer to 72 or the System Smoke Detector Application Guide from Silent Knight GUIDE wiring must be installed in compliance with the National Code applicable local codes and any special of the Authority Having Jurisdiction Proper wire should be used The installation wires should be color to limit wiring mistakes and ease system troubleshooting connections will prevent a system from responding in the event of a fire power from the communication line before sensors Wire the sensor base supplied separately per the wiring Set the desired address on the sensor address switches see Figure 1 Figure 2 Install the sensor into the sensor base Push the sensor into base while turning it clockwise to secure it in place After all sensors have been installed apply power to the unit and activate the communication line Test the sensor s as described in the TESTING section of manual covers provide limited protection against airborne dust during shipment Dust covers must be removed the sensors can sense smoke Remove the sensors to heavy remodeling or construction Plug in Intelligent Sensor Installation Maintenance Instructions to 32 VDC 24 VDC Voltage Range Avg Standby Current Alarm Current LED on 6.5 mA 24 VDC Humidity Range 10 to 93 Relative Temperature Range sensor must be installed in compliance with the control system installation manual The installation must the requirements of the Authority Having Jurisdiction Sensors offer maximum performance when installed compliance with the National Fire Protection Association see NFPA 72 non ondensing to 49 32 to 120 inches 51 mm installed IDP 6AB Base inches 155 mm in IDP 6AB Base inches 104 mm in B501 Base oz 153 g ANNUNCIATOR RETURN LOOP 1 Wiring Diagram 0 2 0 IDP Ion includes a tamper resistant capability that prevents removal from the bracket without the use of a tool Refer to the manual for details on making use of this capability testing notify the proper authorities that the system is maintenance and will temporarily be out of service the system to prevent unwanted alarms sensors must be tested after installation and periodically Testing methods must satisfy the Authority Having gently pushing it until it locks into place Reinstall the detector Test the detector as described in TESTING Reconnect disabled circuits Notify the proper authorities that the system is back on line Test Magnet Status Test Magnet 3 Test Magnet Positioning s 4 Cleaning Screen sensor can be functionally tested with a test The test magnet electronically simulates in the sensing chamber testing the sensor and connections to the control panel Hold the test magnet in the magnet test area as in Figure 3 The sensor should alarm the panel LEDs on the sensor are controlled by the panel indicate sensor status Coded signals transmitted the panel can cause the LEDs to blink latch on latch off Refer to the control panel technical or sensor LED status operation and delay to alarm AHJ Sensors offer maximum performance when and maintained in compliance with NFPA 72 the sensor as follows Functional Magnet Test P N M02 04 01 or M02 09 00 Smoke Entry Aerosol Generator Gemini 501 or other listed devices removing the detector notify the proper authorities the smoke detector system is undergoing maintenance and be temporarily out of service Disable the zone or system maintenance to prevent unwanted alarms Remove the sensor to be cleaned from the system Remove the sensor cover Press firmly on each of the four GEMINI model 501 aerosol generator can be for smoke entry testing Other UL listed smoke devices may be used as well Set the to represent 4 ft to 5 ft obscuration as in the GEMINI 501 manual Using the bowl applicator apply aerosol until the panel alarms sensor that fails any of these tests should be cleaned described under CLEANING and retested If the fails after cleaning it must be replaced testing is complete restore the system to normal and notify the proper authorities that the is back in operation tabs that hold the cover in place Vacuum the outside of the screen carefully If further is required continue with Step 4 otherwise skip to 5 Use clean compressed air to remove dust and debris from sensing chamber Replace the cover using the LEDs to align the cover and Meridian Circle Grove MN 55369 4927 800 328 0103 763 493 6475 2005 Silent Knight refer to insert for the Limitations of Fire Alarm Systems Statement device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this must accept any interference received including interference that may cause undesired operation This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help 2