Silent Knight SWIFT Instructional Manual for WSK-HEAT
File Preview
Click below to download for free
Click below to download for free
File Data
Name | silent-knight-swift-instructional-manual-for-wsk-heat-2461837950.pdf |
---|---|
Type | |
Size | 887.28 KB |
Downloads |
Text Preview
I Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 AND MAINTENANCE INSTRUCTIONS WSK HEAT ROR Intelligent Sensors Operating Voltage Standby Current Current Transmit RF Power Frequency Range Humidity Range Temperature Temperature Rating Detection Type Life Replacement VDC mA MHz to 93 Relative Humidity Non condensing to 100 0 to 38 57 WSK HEAT and WSK HEAT ROR to greater than 15 WSK HEAT ROR Panasonic CR123A or 4 Duracell DL123A year minimum TROUBLE BATTERY LOW display and or during annual maintenance 61 mm installed in B501W Base 102 mm installed in B501W Base oz 230 g installed in B501W base with 4 batteries sensor must be installed in compliance with the control panel system manual and the SWIFT Wireless Manual The installation must the requirements of the Authority Having Jurisdiction AHJ Sensors maximum performance when installed in compliance with the National Protection Association NFPA see NFPA 72 DESCRIPTION WSK HEAT and WSK HEAT ROR are intelligent sensors that utilize a thermistor sensing circuit for fast response These sensors are to provide open area protection with 50 foot spacing capability as by UL 521 Model WSK HEAT is a fixed temperature sensor with fixed temperature alarm Model WSK HEAT ROR is a rate of rise tem sensor with 135 F fixed temperature alarm Rotary dial switches are for setting the sensor address Figure 1 Two LEDs on the sensor controlled by the panel to indicate sensor status Knight panels offer different features sets across different models As a certain features of the WSK HEAT and WSK HEAT ROR may be avail on some control panels but not on others The possible features available the WSK HEAT and WSK HEAT ROR if supported by the control panel are The panel controls the LED operation on the sensor Operational modes red green and amber colors in various solid or blink patterns refer to the operation manual for the UL listed control panel for specific of the WSK HEAT and WSK HEAT ROR WSK HEAT and WSK HEAT ROR require compatible addressable com to function properly Connect these sensors to listed compatible panels only technologies can exhibit communication disruption if devices are too close together To avoid this form of disruption SWIFT devices not be placed closer than 2 feet 60 cm apart without an intervening Do not attach the base and detectors to temporary structures such as ceiling tiles such that the placement could be altered To prevent in device placement permanently secure the structure or mount the across the ceiling panel support as shown in Figure 2 REPLACEMENT battery levels on the wireless devices are displayed as a trouble on an Therefore when the message BATTERY LOW is dis replace the battery in the device This message is an indication that one week of battery life remains replace the batteries in a wireless device use the following steps Have 4 CR123A or DL123A batteries available Remove the detector from the base Open the battery compartment refer to Figure 3 Note The battery compart cover may be left attached at the hinges during battery replacement Remove the used batteries and replace with new batteries The battery is designed such that the batteries can only align in the ap direction Do not force the batteries into the openings Replace the battery compartment cover Return the device to its original location covers provide limited protection against airborne dust particles during Dust covers must be removed before the sensors can sense smoke sensors prior to heavy remodeling or construction RESISTANCE WSK HEAT and WSK HEAT ROR include a tamper resistant capability prevents their removal from the base without the use of a tool Refer to base manual for details on making use of this capability The base also a magnet for tamper resistance The magnet activates a supervisory fault at the panel if the detector is removed from the base testing notify the proper authorities that the system is undergoing and will temporarily be out of service Disable the system to 1 ROTARY ADDRESS SWITCHES 0 0 the zone or system undergoing maintenance to prevent unwanted alarms is recommended that the sensor be removed from its mounting base for cleaning and that sensors be cleaned at least once a year Use a vacuum to remove dust from the sensing chamber Figure 5 NOTE REGARDING SMOKE DETECTOR GUARDS detectors are not to be used with detector guards unless the combina has been evaluated and found suitable for that purpose 2 CEILING PANEL SUPPORT 3 BATTERY COMPARTMENT unwanted alarms sensors must be tested after installation and periodically thereafter Testing must satisfy the Authority Having Jurisdiction AHJ Sensors offer max performance when tested and maintained in compliance with NFPA 72 sensor can be tested in the following ways Functional Magnet Test P N M02 04 01 or M02 09 00 Place the optional test magnet against the cover in the magnet test as shown in Figure 4 to activate the test feature The LEDs should latch on within 10 seconds indicating alarm and an the panel Reset the detector at the system control panel Direct Heat Method Hair dryer of 1000 1500 watts 1 From the side of the detector direct the heat toward the sensor Hold heat source about 6 inches 15 cm away to prevent damage to the during testing The LEDs on the detector should light when the temperature at the reaches the alarm setpoint If the LEDs fail to light check the to the detector and the wiring in the detector base Reset the detector at the system control panel sensor that fails any of these tests should be cleaned as described under and retested If the sensor fails after cleaning it must be replaced returned for repair testing is complete restore the system to normal operation and notify proper authorities that the system is back in operation removing the detector notify the proper authorities that the smoke de system is undergoing maintenance and will be temporarily out of service 4 MAGNET TEST MARKERS MAGNET 5 DETECTOR COMPONENTS CLASSIFICATION ratings are for installations which must comply with FM 3210 RTI RTI refer to insert for the Limitations of Fire Alarm Systems of these products in combination with non Honeywell products in a wireless mesh or to access monitor or control devices in a wireless mesh nework via the inter or another external wide area network may require a separate license from Sipco LLC more information contact Sipco LLC or Ipco LLC at 8215 Roswell Rd Building 900 950 Atlanta GA 303350 or at www sipocollc com or www intusiq com device complies with part 15 of the FCC Rules Operation is subject to the following two conditions This device may not cause harmful interference and This device must accept any interference received including interference that may cause undesired operation Do not make changes to the equipment Changes or modifications not expressly approved by the manufacturer could void the user authority to operate the equipment Knigh and Honeywell are registered trademarks of Honeywell International Inc Honeywell 03 02 STATEMENT STATEMENT