Simplex 4006-9101, 4006-9102, 4006-9121, 4006-9122, 4006-9801, 4006-9802, 4006-9803, 4006-9804, 4006-9805, 4006-9806 4006 Series Conventional Fire Alarm Control Panels providing up to 10 IDCs and up to 4 NACs
File Preview
Click below to download for free
Click below to download for free
File Data
Text Preview
ULC CSFM Listed FM Approved NYC Acceptance Fire Alarm Control Panels 4006 Series Fire Alarm Control Panels up to Ten IDCs and Four NACs panel operator convenience features Wide viewing angle 2 x 20 40 character alphanumeric and dedicated LEDs provide convenient panel information Operation is programmable using a multi function and the panel LCD or via service computer PC RS 232 service port provides upload download PC for panel configuration and event history logs Software updates are via PC download Convenient library of standard custom label terms Standard on board DACT provides Contact ID 3 1 4 2 and SIA formats WALKTEST silent or audible system test Voltage and current for both the battery charger and the can be displayed at the front panel LCD Standard Initiating Device Circuits IDCs Five Class B IDCs with optional expansion to ten all individual zone disable Monitor 2 wire or 4 wire initiating devices including smoke detectors Optional Class A Adapter Module Standard Notification Appliance Circuits NACs Class A or Class B outputs with solid state overcurrent per NAC each rated for 2 A Selectable for Simplex SmartSync two wire control or synchronized strobe control Power Supply Provides 3 A maximum nominal 24 DC Automatic input power selection operates with 120 VAC 240 VAC 50 or 60 Hz On board temperature compensated battery charger for to 12.7 Ah batteries in cabinet UL and ULC and up 25 Ah batteries in separate cabinet UL only standard features Programmable Active Status Reminder Two auxiliary relays NACs and Relay outputs are power limited AC battery circuits and City Circuit Module outputs non power limited Available with beige or red cabinet UL listed to Standard 864 option modules Door mounted 24 LED annunciator standard on ULC 3 A Expansion Power Supply with two on board 2 A that operate the same as standard NACs Beige Standard Control Panel i r e A l a r m A n n u n c i a t o r AND C POWER Beige Control Panel with 24 LED Annunciator option modules Continued Expansion IDC module with five Class B IDCs Class A IDC Adapter Module City Interface Module Auxiliary Relay Module Remote LCD and LED Switch Annunciators areas requiring from five to ten initiating zones the 4006 Series fire alarm control panels provide initiating circuit monitoring extensive control capability and LCD annunciated 20 character custom labels See page 2 for additional ULC and MEA information This product has been approved by California State Fire Marshal CSFM pursuant to Section 13144.1 of the California and Safety Code See CSFM Listing 7165 0026 318 for allowable values and or concerning material presented in this document It is subject to re examination and possible cancellation Additional listings may be applicable contact your local product supplier for the latest status Listings and approvals under Simplex Time Co are the property of Tyco Fire Protection Products 8 2012 Standard Feature Details Class B IDCs are each capable of supporting up to 30 current limited smoke detectors or electronic heat see list on page 4 as well as manual stations and compatible contact closure initiating devices IDCs capable of Class A operation with an optional adapter and can be programmed as Style C short or open a trouble for use with current limited devices only 2 A On Board NACs provide conventional reverse operation selectable as Class A or Class B with control and overcurrent protection Operation is for synchronized strobe or SmartSync horn strobe operation Horn control can be selected at the panel Temporal pattern coding Steady On Slow March Time 20 beats per minute BPM or Fast March Time of BPM Note When selected for SmartSync horn strobe March Time produces 60 BPM 24 VDC Auxiliary output provides up to 500 mA system use Auxiliary output current is counted for power supply capacity Auxiliary Relay Outputs Two relay outputs available selectable as normally open or normally rated 2 A 30 VDC per below Relay 1 is normally assigned to General Alarm but is programmable see page 7 Relay 2 Trouble is energized when Normal and is with a Trouble condition Dual Line DACT Operation can be selected Contact ID SIA 3 1 4 2 and BFSK formats includes Alarm Supervisory Trouble and AC Operation includes automatic 24 hour test and power fail report delay Product Selection Panel Description fire alarm control panel Beige Red Beige Fire alarm control panel with 24 LED Red Modules on front door Standard Feature Details Continued Supply and Battery Charger DC power output 3 A 24 VDC for panel use The temperature battery charger sealed lead acid batteries is rated for up to 25 Ah batteries per UL 864 and up 12.7 Ah per ULC S527 Up to 12.7 Ah batteries fit in cabinet larger batteries require an external cabinet electronics can measure and display voltage and for the power supply batteries and the battery standard and expansion power supply Depleted trouble is monitored and annunciated and depleted cutout can be selected Active battery status supervises charger operation Feature Details Power Supply Provides 3 A total VDC two additional 2 A NACs and an additional power output of 500 mA Output operation is the as on the standard power supply IDC Module Provides 5 additional Class B with operation the same as the standard IDCs Relay Module Provides 10 programmable jumper selectable as N O or N C Contacts are 2 A 30 VDC Typical application is to track of each IDC See page 7 for relay program options A Adapter Module Converts 5 IDCs from B to Class A operation Two modules can be for use with the Expansion IDC Module Circuit Modules These modules are available with without on board disconnect switches depending on requirements either type can be disconnected the front panel under password control are for Remote Station reverse polarity or Master local energy Reporting includes Supervisory and Trouble FM CSFM Feature Summary Class B IDCs 2 Class B Class A 3 A power supply with battery on board DACT 120 240 VAC Hz autoselect Expansion Power Supply 3 A with 2 NACs 120 240 VAC 50 60 Hz Expansion IDC Module 5 Class B IDCs Expansion Relay Module 10 relays selectable as either N O or N C Class A Adapter Module converts 5 IDCs from Class B to Class A City Circuit Module with disconnect switch City Circuit Module without disconnect switch up to one of each as required up to two maximum one if required Beige semi flush trim kit 1 7 16 37 mm wide includes four corners and trim pieces for top bottom and sides Red semi flush trim kit 1 7 16 37 mm wide includes four corners and trim pieces for top bottom and sides Beige External Battery Cabinet for up to 25 Ah batteries mounts close nippled to control panel cabinet dimensions 12 Volt select one battery model per system standby requirements order quantity of two W x 13 1 2 H x 5 3 4 D 413 mm x 343 mm x 146 mm depth increased for 25 Ah effective 7 2005 Ah Ah 12.7 Ah cabinet mount Ah Requires 4009 9801 External Battery Ah UL listed only 8 2012