Simplex 4090-9002 IDNet Relay IAM Installation Instructions
File Preview
Click below to download for free
Click below to download for free
File Data
Name | simplex-4090-9002-idnet-relay-iam-installation-instructions-3562079418.pdf |
---|---|
Type | |
Size | 782.13 KB |
Downloads |
Text Preview
Mechanically Installing the Relay IAM the Relay IAM into a UL Listed 4 inch back box not supplied using Figure 4 as a reference Mount IAM to the back box as follows Loosen the two screws on the square back box Mount the IAM to the back box using the teardrop holes on the mounting bracket Secure the IAM to the back box using the two 8 32 panhead screws 8 32 Panhead Screw Supplied Square Deep Box Supplied IAM U L Listed Back Box Cover Supplied 6 32 Flathead Screw 4 Supplied When wiring the Relay IAM provide a minimum of spacing between IDNet wiring and wiring Use separate conduit entries if the contacts are switching non power limited power When both power limited and non power limited sources are present use type FPL FPLR FPLP power limited cable for power limited circuits Simplex offers semi flush and surface covers ordered separately with a light pipe The cover s with pipe allow viewing of the communications LED without taking the cover off Installation of the semi flush cover and 4090 9802 surface cover are detailed in publication 4090 IDNet Covers and IAM BracketInstallation Instruction 574 796 4 Relay IAM Back Box Installation IDNet Relay IAM Instructions and Warnings NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED Upon unpacking Simplex product inspect the contents of the carton for shipping damage If damage is apparent file a claim with the carrier and notify Simplex HAZARD Disconnect electrical power when making any internal adjustments or repairs should be performed by qualified Simplex Representatives HAZARD Static electricity can damage components Ground yourself before opening or components 4090 9002 Relay Individual Addressable Module IAM provides the 4010 Fire Alarm Control Panel control of one dry form C contact set Normally Open Normally Closed and Common The IAM its current state back to the 4010 FACP for confirmation of operation via the IDNet channel The channel provides the communication link between IAM and 4010 FACP and powers the entire Relay circuitry IAM installation consists of the following Setting the Relay IAMs address Making electrical connections to the Relay IAM Mechanically installing the Relay IAM Re sealable Label Switch The LED flashes approximately once every three to indicate valid communications with the FACP 1 Relay IAM Installation E 2000 Simplex Time Recorder Co Westminster MA 01441 0001 specifications and other information shown were current as of publication and are subject to change without notice is a trademark of Simplex Time Recorder Company E the Relay IAMs Address Relay IAM has a unique address 1 through 250 The address of the IAM is set via an eight position switch Figure 1 DIP switch position 1 is the least significant bit LSB and position 8 is the most bit MSB Set the IAMs address using Figure 2 as reference Use a small screwdriver or pen to the switches The device address for the Relay IAM should be written on the re sealable label this provides an aid in troubleshooting the system DIP switch in position is while DIP switch in position is IS SHOWN SET AT ADDRESS 7 ON OFF SWITCHES 5 THRU 8 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111 128 144 160 176 192 208 224 240 129 145 161 177 193 209 225 241 130 146 162 178 194 210 226 242 131 147 163 179 195 211 227 243 116 132 148 164 180 196 212 228 244 117 133 149 165 181 197 213 229 245 118 134 150 166 182 198 214 230 246 119 135 151 167 183 199 215 231 247 120 136 152 168 184 200 216 232 248 121 137 153 169 185 201 217 233 249 122 138 154 170 186 202 218 234 250 123 139 155 171 187 203 219 235 124 140 156 172 188 204 220 236 125 141 157 173 189 205 221 237 126 142 158 174 190 206 222 238 127 143 159 175 191 207 223 239 2 Relay IAM Address Chart the Relay IAM to the 4010 panel using the 4010 Fire Alarm PC Programmer Installation Programming Instructions 574 187 and 4010 Fire Alarm Front Panel Installing Operating and Instructions 574 052 Refer to 4010 panel label 526 444 for appropriate revision of the to be used Electrical Connections to the Relay IAM and output signals connect to the Relay IAM via the terminals 1 8 as illustrated in Figure 1 connections for the IAM are illustrated in Figure 3 Do not loop wire under terminals Break wire runs to provide supervision Used Note1 Closed N C Used Open N O Note 2 Next Device When connecting two wires to one terminal position one wire on each side of the terminal screw allowable run from 4010 to farthest device not to exceed 2500 feet Refer to Field Wiring 842 073 for further information on wiring Relay IAMs Refer to 4010 panel label 526 444 appropriate revision of the Field Wiring Diagram to be used IDNet wiring is supervised and Contractor wiring to relay contacts is unsupervised use 14 AWG or to local code requirement Relay wiring is only power limited if switching power is provided by the 4010 FACP or a UL listed power supply for fire protective signaling systems 3 Relay IAM Connections