Simplex 4090-9117 Addressable Power Isolator - Installation Instructions

File Preview
File Preview
Click below to download for free

Text Preview

Cautions and Warnings Addressable Power Isolator Instructions NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS Upon unpacking your Simplex product inspect the contents of carton for shipping damage If damage is apparent immediately file a claim the carrier and notify Simplex HAZARD Disconnect electrical power when making any adjustments or repairs Servicing should be performed by qualified Representatives HAZARD Static electricity can damage components Therefore as follows Ground yourself before opening or installing components Keep uninstalled component wrapped in anti static material at all times 4090 9117 Addressable Power Isolator is an addressable device that short circuit and earth fault protection on a 4100U Fire Alarm Control FACP power circuit When a short is detected on the power circuit an Power Isolator module connected between the power supply and short shall automatically open the power circuit The 4100U FACP the Addressable Power Isolator to open or close the lines on command it can be used to locate earths or shorts on the power circuit The IDNet provides the communication link between Addressable Power Isolator FACP and powers the circuit range of possible temperatures under which the 4090 9117 Addressable Isolator may function are between 0 C 32 F and 49 C 120 F 4090 9117 Addressable Power Isolator operates normally under non humidity conditions up to 93 with relative humidity at 32 C 90 F Power Isolator installation consists of the following Setting the Addressable Power Isolator address Making electrical connections to the Addressable Power Isolator Mechanically installing the Addressable Power Isolator Power Power Note DIP The LED flashes approximately once three seconds to indicate valid with the FACP 1 Addressable Power Isolator Assembly 2001 Simplex Time Recorder Co Westminster MA 01441 0001 USA specifications and other information shown were current as of publication and are subject to change without notice is a trademark of the Simplex Time Recorder Company B the Addressable Isolator Address The IDNet channel supports address codes 1 through 250 Addressable Power Isolator has a unique address The address of the Power Isolator is set via an eight position dip switch Figure 1 switch position 1 is the least significant bit LSB and position 8 is the most bit MSB Set the Addressable Power Isolator address using Figure as reference Use a small screwdriver or pen to set the switches The device for the Addressable Power Isolator should be written on the re sealable this information provides an aid in troubleshooting the system DIP switch in position is while DIP switch in position is IS SHOWN SET AT ADDRESS 7 ON OFF SWITCHES 5 THRU 8 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111 128 144 160 176 192 208 224 240 129 145 161 177 193 209 225 241 130 146 162 178 194 210 226 242 131 147 163 179 195 211 227 243 116 132 148 164 180 196 212 228 244 117 133 149 165 181 197 213 229 245 118 134 150 166 182 198 214 230 246 119 135 151 167 183 199 215 231 247 120 136 152 168 184 200 216 232 248 121 137 153 169 185 201 217 233 249 122 138 154 170 186 202 218 234 250 123 139 155 171 187 203 219 235 124 140 156 172 188 204 220 236 125 141 157 173 189 205 221 237 126 142 158 174 190 206 222 238 127 143 159 175 191 207 223 239 2 Addressable Power Isolator Address Chart the Addressable Power Isolator to the 4100 panel using the 4100 Fire PC Programmer Programming Manual 574 849 Configuration Electrical Connections the Addressable Power and output signals connect to the Addressable Power Isolator via terminals TB2 and TB3 as illustrated in Figure 1 Terminal connections for the Power Isolator are illustrated in Figure 3 Do not loop wire under terminals Break wire runs to supervision CURRENT DRAW ADDRESSABLE ISOLATOR 10mA 24VDC FACP FACP STYLE 4 NEXT DEVICE USED STYLE 6 NEXT DEVICE FACP STYLE 4 TO NEXT DEVICE IF USED STYLE 6 TO NEXT DEVICE or FACP STYLE 4 TO NEXT DEVICE IF USED STYLE 4 TO DEVICE USED STYLE 6 TO DEVICE or FLOOR NEXT IDNet and POWER WIRING IDNet and POWER RISER Maximum allowable run from FACP to farthest device not to exceed 2500 feet Maximum total wire including all T Taps from STYLE 6 TO NEXT DEVICE or FACP is 10000 feet IDNet lines are 18 AWG twisted pair shield recommended Allowable voltages 18 VDC 32 VDC Maximum current 2 amps Addressable Power Isolator counts as 1 unit load Refer to Field Wiring Diagram 842 073 for further information on wiring Addressable Power Isolator to IDNet IDNet wiring is and Power Limited 3 Addressable Power Isolator Connections Supplied Installing the Power Isolator the Addressable Power Isolator into a grounded 4 inch U L Listed back not supplied using Figure 4 as a reference Mount the Addressable IDNet to the back box as follows Loosen the two screws on the square back box Mount the Addressable Power Isolator to the back box using the teardrop holes Secure the Addressable Power Isolator to the back box using the two 8 32 the mounting bracket screws Panhead Screw Supplied Listed Square 2 Inch Deep Box Supplied Power Isolator Flathead Screw Supplied Simplex offers semi flush and surface covers ordered separately with light pipe The cover s with light pipe allow viewing of the LED without taking the cover off Installation of the semi flush cover and 4090 9807 surface cover are detailed publication 4090 IDNet Semi Flush Surface Covers and IAM Installation Instruction 574 796 4 Addressable Power Isolator Back Box Installation B

Related Files