Simplex 4098-9806 TrueAlarm Sensor Guard Installation Instructions

File Preview
File Preview
Click below to download for free

Text Preview

SSimplex Sensor Guard 4098 9806 TrueAlarm Sensor Guard is intended ceiling or sidewall mounting as follows Figure 1 Seal electrical box using 3M Weatherban 606 or equivalent Using the template on page 3 Figure 2 drill four holes for appropriate anchoring per local building codes After sensor and base are installed see Notes A B C below secure mounting plate using four i 4 diameter not furnished sensor base is a 4098 9781 Use 4098 9701 sensor only see Warning below Refer to Simplex Publication PER 21 01 5 or PER 21 037 when installing sensor base 9783 or 9786 only Attach hinged side of cover to mounting plate using three 6 32 x l 8 screws and three No 6 lockwashers Attach the three threaded spacers the three i 4 20 x 5 8 screws tamper resistant Place cover in its closed position secure cover using the three l 4 20 x 5 8 screws tamper resistant Use 4098 9823 to install screws Do not paint sensor guard BOX FURNISHED BASE WARNING BELOW USE ONLY A 4098 9701 SENSOR A RESTRICTED SENSITIVITY OF 0.5 TO 1.5 PER FT REFER TO 2120 CONFIGURATION REPORT OR CONTROL EQUATION LISTING REPORT 4020 OR 4100 VERIFY SENSITIVITY RANGE SPACER GUARD 1 SENSOR GUARD WITH 4098 9781 9783 OR 9786 SENSOR BASE Analog Detection is protected by U S Patent No 5.155.466 Detector Base is protected by U S Patent No 5,173.663 1995 Simplex lime Recorder Co Gardner MA 01441 0001 U S A specifications and other information shown were current as of publication and are subject to change without notice 12 95 HOLE CHART GANG BOX OCTAGONAL BOX SQUARE BOX LOCATIONS 2 TEMPLATE 12 95