Simplex 4903 TrueAlert Non-Addressable SmartSync Audible-Visible Installation Instructions

File Preview
File Preview
Click below to download for free

Text Preview

4903 TrueAlert Non Addressable Audible Visible Instructions and Warnings NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product inspect contents of the carton for shipping damage If damage is apparent immediately file a claim with the carrier and notify Simplex HAZARD Disconnect electrical power when making any internal adjustments or repairs should be performed by qualified Simplex Representatives HAZARD Static electricity can damage components Therefore handle as follows Ground yourself before opening or installing components Keep uninstalled component wrapped in anti static material at all times use the 553 484 Static Control Kit FREQUENCY ENERGY This equipment generates uses and can radiate radio frequency energy and not installed and used in accordance with the instruction manual may cause interference to radio It has been tested and found to comply with the limits for a Class A computing device pursuant Subpart J of Part 15 of FCC Rules which are designed to provide reasonable protection against such when operated in a commercial environment Operation of this equipment in a residential area may interference in which case the user at his own expense will be required to take whatever measures may be to correct the interference Non Addressable SmartSync A V Operation 4903 TrueAlert Audible Visible A V units see Figure 1 are non addressable wall Notification Appliances that provide an audible and or visible warning of an alarm condition when activated from the control panel of a UL listed Fire Alarm System When the Notification Appliance emits sound and or it indicates the possibility of an emergency situation that requires your attention A V Unit is a Notification Appliance that operates on a reverse polarity Notification Circuit NAC When this NAC is in the reverse polarity or supervision these appliances do not operate and present a high impedance to the circuit They when the NAC changes polarity entering the state wall mounted A V Unit activates a high intensity pulsed light output with sounder at a rate that is determined by A V configuration The A V to a synchronization signal received from the NAC The A V strobe flashes when it detects SmartSync synchronization signals from the NAC A V horn cadence is determined by a coded message within the SmartSync The SmartSync A V can only be operated through a SmartSync Control 4905 9938 4010 Fire Alarm Control Panel or 4009 IDNet NAC are 3 models of each of the of the A V versions each has a different light output rating 15 candela 75 candela and 110 candela A V are available in red and white color versions Table 1 Table 2 and Table 3 describe A V features current ratings and sound pressure measurements 1 TrueAlert A V 1 Wall Mounted TrueAlert Non Addressable A V Feature Chart WIRE A V 15 CANDELA WIRE A V 75 CANDELA WIRE A V 110 CANDELA WIRE A V 15 CANDELA WIRE A V 75 CANDELA WIRE A V 110 CANDELA ID PID NUMBERS COVER COLOR 2000 Simplex Time Recorder Co Westminster MA 01441 0001 USA specifications and other information shown were current as of publication and are subject to change without notice and SmartSync are trademarks of Simplex Time Recorder Company E Non Addressable SmartSync A V Wiring Make sure that all electrical power is disconnected before starting the installation Connect wiring to terminals as shown Do not loop wires under terminals Break wire runs to provide of connections Do not bring conduit through the rear of the electrical box Strip lead to 3 8 inch maximum At the enclosure box run contractor wiring through the cutout slot and connect the wires to the NAC and NAC at the front of the A V unit Torque terminal block screws 12 15 in lbs to ensure proper continuity See 2 When connecting more than one A V to a circuit ensure that correct polarity is maintained for each A V unit When connecting the last A V unit on a circuit connect an end of line resistor EOLR to the A V terminals SLOT FOR WIRING AWG NOTES 2 INPUT 1 INPUT TERMINALS ACCEPT WIRES 12 18 AWG VDC POWER INPUT NOTE 4 A V LAST APPLIANCE ON CONNECT EOLR NOTES 16 33 VDC NON NOTIFICATION CIRCUIT OR APPLIANCE NOTES A V Notification Appliances are rated per individual nameplate label Maintain correct polarity on terminal connections Do not loop wires under terminals Refer to the Field Wiring Diagrams supplied with the FACP for detailed NAC wiring information appliances were only tested to the operating voltage limits of 16VDC and 33VDC Do not operate these appliances outside limits doing so may cause appliance to fail to operate and or cause permanent damage to this equipment TrueAlert Non Addressable SmartSync A V can only be operated through a SmartSync Control Module 4905 9938 4010 Fire Control Panel or 4009 IDNet NAC Extender Maximum 35 appliances per circuit Maximum 30 ohms wire resistance between appliances Refer to the Field Wiring Drawings of driving Fire Alarm Control Panel for further instructions 2 TrueAlert SmartSync A V Wiring the TrueAlert Non Addressable SmartSync A V Figure 3 for mounting the TrueAlert SmartSync A V to the enclosure box When surface mounting the A V the 4905 or 4905 9940 TrueAlert Surface Mount Skirt is recommended Refer to the 4905 TrueAlert NAC Surface Mount Skirt Instructions 574 790 for this mounting application Do not bring conduit through the rear of the electrical box Tighten screws snugly do not overtighten Torque mounting screws 5 7 in lbs For semi flush mounting install the box either flush with the wall or with a maximum 0.25 inch recess HOLES FOR MOUNTING NOT SUPPLIED NOTES 1 and 2 HOLES FOR 4 SQUARE MOUNTING SUPPLIED NOTES 1 and 2 FROM 748 472 GROUP QTY 2 SCREWS COVER HOLES FOR MOUNTING NOT SUPPLIED NOTES 1 and 2 SQUARE BOX SUPPLIED NOTES 1 and 2 NOTE 3 TrueAlert A V unit attaches directly to standard single gang double gang and 4 inch square electrical not supplied mounted semi flush or surface to the wall surface The two mounting screws are placed corner opposite top and bottom holes are two holes for single gang and double gang electrical box mounting secure the housing to the single or double gang box using two mounting screws 6 32 x 1 1 8 inch long not supplied The two mounting are placed cross corner opposite top and bottom holes for the double gang installation remove cover press snap release in one at a time with a flat tip screwdriver while pulling up cover with hand 3 TrueAlert A V Mounting 2 TrueAlert A V Units Strobe Current Rating Chart VDC mA mA Avg mA NOTE 1 Current is measured with the horn steady on 3 TrueAlert A V Units Sound Pressure Level Measurements PRESURE LEVEL MEASUREMENT dBA ROOM AT TEN FEET ROOM TEN FEET PER UL464 NOTE 2 NOTE 3 The coded category covers both Temporal and March Time cadences Average anechoic dBA measurements are measured on axis in a non reflective test chamber using fast meter response Reverberant dBA measurements are a minimum UL rating based on sound power level measurements made in UL reverberant

Related Files