Goal How to add a 2001 2076 Signal Module 2001 2001 8001 2001 1007 Control Module 556 880 2001 2076 Dual Class B Signal Module 556 874 Polarity not reversing Not reporting trouble No supervision voltage on the signal circuit No Signal Power No output signal Need module information Adding additional signals to panel Module modifications are common in 2001 systems to perform specific custom operations Always note revision and jumper settings and any component removed from any 2001 module being Check for the Follow D 25 on Control module 556 880 is not removed March time module 520 564 is not installed Insure the jumpers are installed for each signal circuit The jumper is located between 15 16 Zone and 29 30 Zone 2 on the Signal module 556 874 Signal Wiring a Signal Circuit 1 P is Negative and N is Positive b Signal Circuit 2 S is Positive and 13 is Negative The Signal Card is power a Resettable Power 24VDC A Buss Left Hand Terminal Strip 12 b Signal Circuit 1 and 2 supervision and alarm voltage 24VDC comes from the B Buss Left Hand Strip 1 first mother board or 4 second mother board If fuse F1 or F2 are removed and the system shows trouble but when an open occurs on the signal or no supervision alarm voltage is on the circuit check the B Buss voltage