Simplex How to add a Signal Module into a 2001-9010

File Preview
File Preview
Click below to download for free

File Data

Name simplex-how-to-add-a-signal-module-into-a-2001-9010-2581036974.pdf
Type PDF
Size 570.62 KB
Downloads

Text Preview

Goal How to add a Signal Module into a 2001 9010 2001 SVP 2001 9010 Fire Alarm Voice Communications System 2001 2076 Dual Class B Signal Module 556 874 2001 1017 Dual Zone Module Class B 556 082 Polarity not reversing No output signal Signal Circuits activate for no apparent reason No Signal Power The 2001 9010 has a constant OV on TB1 10 C buss The Signal Module must be configured as if system is coded 556 874 Signal Module remove Jumpers 15 to 16 and 29 to 30 556 082 Signal Module remove D19 and D29 The slot that the Signal Module is install has an F connector above the card slot jumper a wire from F connector 3 or 4 and 1 or 2 to the 556 880 Fire control card F connector 3 for on until or 4 for on until Reset If the Signal Module is installed in the slots 2 through 4 then 24VDC for signal voltage must be wired TB1 1 If the Signal Module is installed in the slots 5 through 8 then 24VDC for signal voltage must be wired TB1 4