Simplex How to Connect Earth Ground the 2001 Repack Series

File Preview
File Preview
Click below to download for free

Text Preview

Goal How to Connect Earth Ground the 2001 Repack Series 2001 2001 8021 Repack 2001 8023 Expanded Repack a Fact 2001 8001 System not reporting Ground Faults Panel has no earth ground reference connected The panel requires a ground for safety and proper function Connect a ground to the chassis and a jumper to the terminal strip as indicated below Panel TB1 1 Located below the Control Module in socket J1 Repack Panel TB1 1 Located to the left of the Control Module in socket J1 See Also the Following Solution How to Connect Earth Ground on a 2001 8000 Series