Simplex How to Get Aux Alm and Tbl Contacts from a Repack

File Preview
File Preview
Click below to download for free

Text Preview

Goal How to Get Auxiliary Alarm and Auxiliary Trouble Contacts from a 2001 Repack or Expanded 2001 2001 8021 Motherboard 556 663 2001 8022 Motherboard 556 663 2001 8023 Motherboard 562 355 2001 8025 Motherboard 562 355 2001 8024 Motherboard 562 355 Alarm output Alarm Contacts Trouble Contacts Relay Unable to locate Alarm Contacts Unable to locate Trouble Contacts Need auxiliary trouble output Need documentation Adding Digital Alarm Communicator Transmitter There is an Alarm relay output only For trouble output panel modification will be required Refer to the 2001 Expanded Panel Training Manual 575 977 Refer to the 2001 Repack Panel Training Manual FA2 91 007 The 562 663 Repack Motherboard has a Alarm relay contact output on TB4 562 355 Expanded Repack Motherboard has a Alarm relay contact output on TB5 is no Trouble relay contact on the 562 663 Repack and 562 355 Expanded Repack Jumper wires need to be soldered on the motherboard interconnection pads and connected to a relay Alarm and Trouble points are as follows For the 562 663 Repack Motherboard Output Normal Open Common Normal Closed Output 13 V out when system trouble 21 0V system common For the 562 355 Expanded Repack Motherboard Output Normal Open Common Normal Closed Output 13 V out when system trouble 14 0V system common Connect a jumper wire from pads 13 21 Repack 562 663 and 13 or 14 Expanded Repack to a external relay such as 2088 9007 Air Product and Controls Inc MR 101

Related Files