Simplex How to Provide Resettable 24V on a Repack or Expanded Repack
File Preview
Click below to download for free
Click below to download for free
File Data
Name | simplex-how-to-provide-resettable-24v-on-a-repack-or-expanded-repack-6103598742.pdf |
---|---|
Type | |
Size | 570.69 KB |
Downloads |
Text Preview
Goal How to Provide Resettable 24V on a Repack or Expanded Repack 2001 2001 8021 Repack 2001 8021 Motherboard 556 663 2001 8023 Expanded Repack 2001 8023 Motherboard 562 355 Unable to locate resettable power Need to reset 4 wire smoke detector Adding 4 wire smoke detector which requires a resettable 24V power source There is no field use resettable 24volt power termination on the panel Order a 556 255 Fused Reset Module The separate disconnect switch on the module is used to drop power for reset operation before resetting the control module The 2 amp fuse protects the panel supply the module and wire device 24V to the N terminal the N terminal number location will depend location installed in the panel 0V terminal will be one of the following Repack 2001 8021 TB4 5 or 6 and or TB3 1 or 2 Exp Repack 2001 8023 TB5 5 or 6 and or TB6 4 5 or 6