Simplex How to Remove Annunciator Supervision from a 2001 Zone

File Preview
File Preview
Click below to download for free

Text Preview

Goal How to Remove Annunciator Supervision from a 2001 Zone Module 2001 2001 1017 Dual Zone Module Class B 556 082 2001 1019 Dual Zone Module Class B w Test Switch 556 896 System trouble led on control card Annunciator trouble led on control card Need module information Replaced Zone Card Module modifications are common in 2001 systems to perform specific custom operations Always note revision and jumper settings and any component removed from any 2001 module being 1 Remove D29 for Zone 1 Remove D19 for Zone 2 This will only remove annunciator supervision for this card On the older style of card LED s side by side the diodes may be hard to locate Holding the edge connector down find the bottom most horizontal row of components D19 is the 4th diode the left and D29 is the 5th On newer style module LED s verticle the layout of components has changed Holding the edge connector down the diodes are in the most bottom row Starting from left side not caps D19 is the 4th component and D29 is the 10th component