Goal How to Set up a Remote Reset Switch on a 2001 panel 2001 2001 1001 Control Module 556 232 2001 1002 Control Module 556 233 2001 1003 Control Module 556 234 2001 1004 Control Module 556 235 2001 1005 Control Module 556 236 2001 1006 Control Module 556 656 2001 1007 Control Module 556 880 Need to add a Remote Reset Switch Remote system reset is not working Need module information need wiring information Replaced module Proper Jumper Not Cut Module modifications are common in 2001 systems to perform specific custom operations Always note revision and jumper settings and any component removed from any 2001 module being For each of the Common Control Boards the jumper associated with the PC Pin Outputs N and S to be cut and a Normally Closed Switch installed For the 2001 1002 1003 1004 the Jumper is as E For the 2001 1006 the Jumper is Labeled as C For the 2001 1007 the jumper is located the on board terminals of 3 and 4 the 2001 1005 a Normally Open Switch is used and a High Going Voltage is applied to PC Pin Input