Goal How to Wire a Remote Acknowledge Switch on a 2001 2001 2001 8021 Repack 2001 3080 2001 8021 Motherboard 556 663 2001 1007 Control Module 556 880 The remote acknowledge on the annunciator does not work Unable to remote acknowledge The Control Module has been replaced replaced module Jumper not cut Always note revision and jumper settings and any component removed from any 2001 module being Module modifications are common in 2001 systems to perform specific custom operations Cut JW1 and make sure the N C switch is located between 2 and R located on the C socket Even this will provide remote acknowledge it will not provide printer functions Also there will be no zone indication that the system has been acknowledged it is required to make the zone LED go steady on acknowledge then use a Dual Relay powered off the switch Wire one set of NC contacts between 2 and R and the second set of contacts wire between 2 and 8 This will put the necessary input to the zone cards and allow for steady zone and printer activation Pins 2 and R are located on the C plug and 8 is at TB1 2 same procedure can be used on the repack again the PC locations are 2 8 and R This converts as Pin 2 Pad 3 Pin 8 Pad 9 Pin R Pad 15 OF THESE CONNECTIONS ARE SUPERVISED