Simplex Transient Suppressor-Zone Disconnect Boards 4001-9804 Transient Suppressor, 4001-9806 Zone Disconnect, & 4001-9807 Combination

File Preview
File Preview
Click below to download for free

Text Preview

BfSimplex Transient Suppressor Zone Disconnect and Combination Transient Disconnect Boards Ensure power the 4001 control is OFF before proceeding INDICATING APPLIANCE SEE STEP 2 board the control panel as shown 1 INITIATING DEVICE SEE 3 4 i electrical connections as follows Connect board ribbon cable harness to board control the blue marked Pl Connect connector Pl Ensure end lines up with pin 9 on each connector other end For the 4001 9804 appliance circuit 10 SIG suppressor board or TBl 9 For the 4001 9804 or 9807 board connect device circuits as indicated Table 1 any of the designated zone terminals on the do not have initiating devices connected them a 3.3K ohm EOLR must be connected those terminals BOARD 1 BOARD If using waterflow or sprinkler connect them as follows Connect water flow switch normally ooen to 5 ZON3 and TBl 6 Connect srxinkler switch TBl 8 NO WIRES ARE CONNECTED TO ZONE A 3.3 K ACROSS THOSE TERMINALS 1 1966 Simplex Recorder Gardner MISS 014414001